Toshiba TOSVERT VF-A5 Instruction Manual page 20

High-performance inverter
Hide thumbs Also See for TOSVERT VF-A5:
Table of Contents

Advertisement

E6580516
Table 5.1: Examples of selecting equipment for wiring
Inverter
Non-fuse breaker
Magnetic
Overload relay
Surge killer
Wire size
(MCCB)
contactor (MC)
Th-Ry
Voltage
Applicable
Model
Rated Toshiba Rated Toshiba
Adjusted
Toshiba
Model
Main
DC
Dynamic
motor
current value
class
(kW)
current
model
current model
(A)
model
(Note 2)
circuit reactor braking
(A)
(A)
(Note 1)
(mm2)
(mm2)
resistor
[Reference
(Note 3)
(mm2)
value]
0.4
-2004P
5
8830
11
C13J
2.3
T13J
2.0
0.75 -2007P
10
8830
11
C13J
3.6
T13J
2.0
1.25
1.5
-2015P
15
8830
11
C13J
6.8
T13J
2.0
-
2.2
-2022P
20
8830
11
C13J
9.3
T13J
2.0
2.0
3.7
-2037P
30
8830
18
C20J
15
T20J
3.5
5.5
-2055P
50
E850
35
C35J
22
T35J
Toshiba
8.0
5.5
7.5
-2075P
60
EH1008
50
C50J
28
T35J
model SS-2
14
11
-2110P
100
EH1008
65
C65J
44
T65J
14
14
5.5
or
200V
15
-2150P
125
EH225
80
C80A
57
T65J
Marcon
22
class
18.5
-2185P
125
EH225
93
C100A
70
T80A
Electronics
38
38
22
-2220P
150
EH225
93
C100A
85
T125A RFM2E224KO 38
22
30
-2300P
200
EH225
180
C180A
108
T125A
60
60
37
-2370P
225
EH225
180
C180A
138
T150A
100
38X2
45
-2450P
250
EH400
220
C220A
162
T180A
100
150
55
-2550P
250
EH400
220
C220A
198
T220A
100
60
75
-2750P
500
EH600
300
C300A
3.2
T400A
100X2
150X2
90
-2900P
600
EH600
400
C400A
4.0
T400A
150X2
0.75
-4007P
5
SS30
9
C13J
2.3
T13J
2.0
1.5
-4015P
10
SS30
9
C13J
3.6
T13J
2.0
1.25
-
2.2
-4022P
10
SS30
9
C13J
5.0
T13J
2.0
3.7
-4037P
15
SS30
9
C13J
6.8
T13J
2.0
5.5
-4055P
30
SS30
17
C20J
11
T13J
3.5
2.0
7.5
-4075P
30
SS30
17
C20J
15
T20J
5.5
3.5
2.0
11
-4110P
50
ES50
33
C35J
22
T35J
Marcon
8
5.5
15
-4150P
60
EH1008
48
C50J
28
T35J
Electronics
8
8.0
3.5
18.5
-4185P
75
EH100B
48
C50J
35
T65J
RFM2H104KD
14
14
400V
22
-4220P
100
EH100B
48
C50J
44
T65J
(400V system) 22
8.0
class
30
-4300P
125
EH225
80
C80A
57
T65J
(Note6)
38
22
37
-4370P
125
EH225
93
C100A
65
T80A
38
38
45
-4450P
150
EH225
180
C180A
85
T125A
38
60
22
55
-4550P
175
EH225
180
C180A
100
T125A
60
75
-4750P
225
EH225
220
C220A
138
T150A
100
100
110
-411 OKP
350
EH400
265
C300A
2.7
T220A
60X2
60X2
132
-4132KP
400
EH400
400
C400A
3.6
T400A
60X2 100X2
60
160
-4160KP
500
EH600
400
C400A
4.2
T400A
100X2 150X2
220
-4220KP
700
E800
600
C600A
CT
T20A
200X2 200X2
80
280
-4280KP
800
E800
600
C600A
CT
T20A
200X2 250X2
(Note 1} When selecting a magnetic contactor (MC) with 2a auxiliary contacts and using the auxiliary
contacts for the control circuit, parallel the 2a contacts to improve contact reliability.
(Note 2} Install a surge killer on the magnetic contactor or relay exciting coil.
(Note 3} The wire sizes for the input side R, S, T and output side U, V, Ware shown. These sizes apply
only when the wiring length is less than 30m. Increase the wire sizes when the length exceeds 30m.
(Note 4} For the control circuit, use the shielded wire of 0.75mm
2
or more in wire size.
(Note 5) Use a wire size 3.5mm
2
or more for the grounding wire.
(Note 6) 200V system: type SS-2 or Marcon Electronics RFM2E224KD
- 14 -