Emerson Dixell XWi70K Installing And Operating Instructions page 5

Standard controller
Table of Contents

Advertisement

FAC
Probe selection for condenser fan: (nP; P1; P2; P3; P4) nP = no probe, regulator
disabled; P1 =thermostat probe; P2 = Second probe; P3 =Third probe; P4 =Fourth
probe.
St2
Set Point for condenser fan regulator: (-100 to 150 °C; -148 to 302°F) set point used
for condenser fan regulator
HY2
Differential for condenser fan regulator: (0.1 to 25.5°C; 1 to 45°F) differential used
for condenser fan regulator
FCC
Condenser fan mode of operation: (C-n; o-n; C-Y; o-Y) C-n = runs with the
compressor, OFF during defrost; o-n = continuous mode, OFF during defrost; C-Y =
runs with the compressor, ON during defrost; o-Y = continuous mode, ON during defrost
FCo
Condenser fan activated when compressor off: (0 to 999 sec) interval with condenser
fan on after stopping compressor and when FCC=C-n or C-Y
LA2
Condenser fan operating hours: (0 to 999) set the warning interval for maintenance.
Internal value is multiplied by 100.
rS2
Reset maintenance alarm for condenser fan: change to Y and confirm with SET
button to reset condenser fan maintenance warning. LA2 interval will be reloaded.
AUXILIARY MENU – AUS
ACH
Type of action for auxiliary regulator: (CL; Ht) CL = cooling; Ht= heating
SAA
Set point for auxiliary regulator: (-100 to 150 °C; -148 to 302°F) set point used for
auxiliary regulator
SHY
Differential for auxiliary regulator: (0.1 to 25.5°C; 1 to 45°F) differential used for
auxiliary regulator
ArP
Probe selection for auxiliary regulator: (nP; P1; P2; P3; P4) nP = no probe, regulator
disabled; P1 =thermostat probe; P2 = Second probe; P3 =Third probe; P4 =Fourth probe
Sdd
Auxiliary regulator disabled during any defrost: (n; Y) n = enabled; Y = disabled
btA
Time base for parameter Ato and AtF: (Min; SEC) Min=base time is in minutes;
SEC=base time is in seconds
Ato
Interval with auxiliary output active: (0 to 255) valid if oAx=tiM, x=0,1,2,3,4 or if
xAo=tiM, x=1, 2
AtF
Interval with auxiliary output not active: (0 to 255) valid if oAx=tiM, x=0,1,2,3,4 or if
xAo=tiM, x=1, 2
ALARM MENU - ALr
ALP
Temperature alarm probe selection: (nP; P1; P2; P3; P4) nP = no probe, the
temperature alarms are disabled; P1 = Probe 1 (Thermostat probe); P2 = Probe 2; P3 =
Probe 3; P4 = Fourth probe.
ALC
Temperature alarms configuration: (Ab; rE) Ab = absolute temperature, alarm
temperature is given by the ALL or ALU values. rE = temperature alarms are referred
to the set point. Temperature alarm is enabled when the temperature exceeds the
[SET+ALU] or [SET-ALL] values.
ALU
Maximum temperature alarm:
 If ALC=Ab: [ALL to 150.0°C or ALL to 302°F]
 If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached, the alarm is enabled after the ALd delay time.
ALL
Minimum temperature alarm:
 If ALC=Ab: [-100°C to ALU; -148°F to ALU]
 If ALC=rE: [0.0 to 50.0°C or 0 to 90°F]
when this temperature is reached, the alarm is enabled after the ALd delay time.
AFH
Differential for temperature alarm recovery: (0.1 to 25.5°C; 1 to 45°F) intervention
differential for recovery of temperature alarm.
ALd
Temperature alarm delay: (0 to 255 min) time interval between the detection of an
alarm condition and alarm signaling.
dot
Temperature alarm delay when door open: (0 to 255 min) delay before activating the
door open alarm
dAo
Temperature alarm delay after power-on: (0.0 to 24h00min, res. 10min) time interval
between the detection of the temperature alarm condition after instrument power on and
temperature alarm signaling. It also delays the display indication of compressor warning
alarms (if serial compressor control is used). NOTE: Modbus status are always updated
with running alarm or warnings, also during dAo delay.
AP2
Second temperature alarm probe selection: (nP; P1; P2; P3; P4)
nP = no probe; P1 = thermostat probe; P2 = second probe; P3 = Third probe; P4 =
Fourth probe.
AL2
Second low temperature alarm: (-100 to 150°C; -148 to 302°F) when this temperature
is reached the LA2 alarm is signaled, possibly after the Ad2 delay.
Au2
Second high temperature alarm: (-100 to 150°C; -148 to 302°F) when this
temperature is reached the HA2 alarm is signaled, possibly after the Ad2 delay.
AH2
Differential for second temperature alarm recovery: 0.1 to 25.5°C; 1 to 45°F.
Ad2
Second temperature alarm delay: (0 to 255 min) time interval between the detection
of the condenser alarm condition and alarm signaling.
dA2
Second temperature alarm activation delay after power-on: 0.0 to 24h00min, res.
10min.
bLL
Compressor off due to second low temperature alarm: (n; Y) n = compressor keeps
on working; Y = compressor is switched off till the alarm is present, in any case regulation
restarts after AC time at minimum.
AC2
Compressor off due to second high temperature alarm: (n; Y) n = compressor keeps
on working; Y = compressor is switched off till the alarm is present, in any case regulation
restarts after AC time at minimum.
SAF
Differential for anti-freezing control: (0.0 to 25.5°C; 0 to 45°F) lower threshold used
to avoid freezing conditions. If T<SET-SAF, then the compressor will be stopped. If
SAF=0 this function is disabled.
tbA
Alarm relay deactivation (with oAx =ALr): (n; Y) n = silencing disabled: alarm relay
stays on till alarm condition lasts. Y = silencing enabled: alarm relay is switched OFF by
pressing a key during an alarm.
bUM
Buzzer muting: (n; Y) n = buzzer cannot be stopped; Y = buzzer activation due to any
alarm can be stopped
1592026640 XWi70K GB r1.0 04.06.2020
OUTPUT CONFIGURATIONS – oUt
oA1
Relay output oA1 configuration, terminals 16-17: (nu; onF; dEF; Fan; Alr; LiG;
(20-21)
Au1; Au2; db; CP1; CP2; dF2; HES; HEt; inV; tiM; Cnd) nu=not used; onF = always
on with instrument on; dEF=defrost; Fan=Fan; Alr=alarm; LiG=light; Au1=auxiliary
output; Au2=auxiliary output 2; db=neutral zone; CP1=ONOFF compressor;
CP2=second ONOFF compressor; dF2=second defrost; HES=energy saving;
HEt=heater output control; inV=inverter output; tiM=timed mode activation;
Cnd=condenser fan
oA2
Relay output oA2 configuration, terminals 20-21: (nu; onF; dEF; Fan; Alr; LiG;
(16-17)
Au1; Au2; db; CP1; CP2; dF2; HES; HEt; inV; tiM; Cnd) nu=not used; onF = always
on with instrument on; dEF=defrost; Fan=Fan; Alr=alarm; LiG=light; Au1=auxiliary
output; Au2=auxiliary output 2; db=neutral zone; CP1=ONOFF compressor;
CP2=second ONOFF compressor; dF2=second defrost; HES=energy saving;
HEt=heater output control; inV=inverter output; tiM=timed mode activation;
Cnd=condenser fan
oA3
Relay output oA3 configuration, terminals 22-23: (nu; onF; dEF; Fan; Alr; LiG;
(18-19)
Au1; Au2; db; CP1; CP2; dF2; HES; HEt; inV; tiM; Cnd) nu=not used; onF = always
on with instrument on; dEF=defrost; Fan=Fan; Alr=alarm; LiG=light; Au1=auxiliary
output; Au2=auxiliary output 2; db=neutral zone; CP1=ONOFF compressor;
CP2=second ONOFF compressor; dF2=second defrost; HES=energy saving;
HEt=heater output control; inV=inverter output; tiM=timed mode activation;
Cnd=condenser fan
oA4
Relay output oA4 configuration, terminals 22-23: (nu; onF; dEF; Fan; Alr; LiG;
(22-23)
Au1; Au2; db; CP1; CP2; dF2; HES; HEt; inV; tiM; Cnd) nu=not used; onF = always
on with instrument on; dEF=defrost; Fan=Fan; Alr=alarm; LiG=light; Au1=auxiliary
output; Au2=auxiliary output 2; db=neutral zone; CP1=ONOFF compressor;
CP2=second ONOFF compressor; dF2=second defrost; HES=energy saving;
HEt=heater output control; inV=inverter output; tiM=timed mode activation;
Cnd=condenser fan
oA5
Relay output oA5 configuration, terminals 29-30-31: (nu; onF; dEF; Fan; Alr;
(29-30-
LiG; Au1; Au2; db; CP1; CP2; dF2; HES; HEt; inV; tiM; Cnd) nu=not used; onF =
31)
always on with instrument on; dEF=defrost; Fan=Fan; Alr=alarm; LiG=light;
Au1=auxiliary output; Au2=auxiliary output 2; db=neutral zone; CP1=ONOFF
compressor; CP2=second ONOFF compressor; dF2=second defrost; HES=energy
saving; HEt=heater output control; inV=inverter output; tiM=timed mode activation;
Cnd=condenser fan
AoP
Alarm relay polarity: (CL; oP) it set if the alarm relay is open or closed when an
alarm occurs. CL = terminals closed during an alarm; oP = terminals open during
an alarm.
DIGITAL INPUT MENU - inP
i1P
Digital input 1 polarity: (oP; CL) oP = the digital input is activated by opening the
contact; CL = the digital input is activated by closing the contact.
i1F
Digital input 1 configuration: (EAL; bAL; PAL; dor; dEF; AUS; Htr; FAn; ES; HdF; LHt;
onF; Lnt) EAL = external alarm: "EA" message is displayed; bAL = serious alarm "CA"
message is displayed; PAL = pressure switch alarm, "CA" message is displayed; dor =
door switch function; dEF = activation of a defrost cycle; AUS = auxiliary relay activation
with oAx=AUS; Htr = type of inverting action (cooling or heating); FAn = evaporator fan
activation; ES = energy saving; HdF = Holiday defrost (enable only with RTC); onF = to
switch the controller off; LHt = to activate the light; Lnt = parameter map change.
did
Digital input 1 alarm delay: (0 to 255 min) delay between the detection of the external
alarm condition and its signalling.
When i1F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
i2P
Digital input 2 polarity: (oP; CL) oP = the digital input is activated by opening the
contact; CL = the digital input is activated by closing the contact.
i2F
Digital input 2 configuration: (EAL; bAL; PAL; dor; dEF; AUS; Htr; FAn; ES; HdF; LHt;
onF; Lnt) EAL = external alarm: "EA" message is displayed; bAL = serious alarm "CA"
message is displayed; PAL = pressure switch alarm, "CA" message is displayed; dor =
door switch function; dEF = activation of a defrost cycle; AUS = auxiliary relay activation
with oAx=AUS; Htr = type of inverting action (cooling or heating); FAn = evaporator fan
activation; ES = energy saving; HdF = Holiday defrost (enable only with RTC); onF = to
switch the controller off; LHt = to activate the light; Lnt = parameter map change.
d2d
Digital input 2 alarm delay: (0 to 255 min) delay between the detection of the external
alarm condition and its signaling.
When i2F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
nPS
Number of pressure alarm events before stopping the regulation (Lock alarm): (0
to 15) Number of activation, during the did or d2d interval, before signalling an alarm
event (i1F, i2F=PAL).
If the nPS activation during did or d2d time is reached, switch off and on the instrument
to restart normal regulation.
odC
Compressor and fan status after door opening: (no; FAn; CPr;F_C;) no = normal;
FAn = normal; CPr = compressor OFF, F_C = compressor OFF.
rrd
Regulation restart after open door alarm: (n; Y) n = outputs follow the odC parameter.
Y = outputs restart with a door open alarm.
ENERGY SAVING MENU – ES
HES
Differential for energy saving mode: (-30 to 30°C; -54 to 54°F) it sets the increasing
value of the set point [SET+HES] during the Energy Saving cycle.
ESt
Time-out for energy saving mode: (0 to 255 hours) maximum duration for energy
saving mode. If ESt=0 then this function is disabled.
LdE
Energy saving mode controls the lights: (n; Y) lights off when energy saving mode is
active
LHt
Time-out for light output: (0 to 255 min) the light output will be forced OFF after this
period. LHt=0 means function disabled.
OTHER
Adr
Serial address: (1 to 247) identifies the instrument address when connected to a
Modbus compatible monitoring system.
bAU
Baudrate for serial communication: 9.6 = 9600baud; 19.2 = 19200baud
onC
ONOFF button configuration: (nU; oFF; ES; SEr) nU = disabled; oFF = enabled; ES
= energy saving mode; SEr = do not use it
dP1
Probe P1 value visualization (read only)
XWi70K
5/8

Advertisement

Table of Contents
loading

Table of Contents