Midea CCM-180A/WS Service Manual page 42

Vrf commercial air conditioners, touch screen centralized controller 6.2-inch
Table of Contents

Advertisement

1
Silent Mode
Mode Priority
Auto Energy
Saving
201803
the master unit, 60% capacity output)
n46: Power limitation mode 6 (Only available for
the master unit, 50% capacity output)
n47: Power limitation mode 7 (Only available for
the master unit, 40% capacity output)
0: Night silent time is 6h/10h (default)
1: Night silent time is 6h/12h
2: Night silent time is 8h/10h
3: Night silent time is 8h/12h
4: No silent mode
5: Silent mode 1 (only limit max fan speed)
6: Silent mode 2 (only limit max fan speed)
7: Silent mode 3 (only limit max fan speed)
8: Super silent mode 1 (limit max. fan speed and
compressor frequency)
9: Super silent mode 2 (limit max. fan speed and
compressor frequency)
A: Super silent mode 3 (limit max. fan speed and
compressor frequency)
B: Super silent mode 4 (limit max. fan speed and
compressor frequency)
F: Set silent mode via the centralized controller (To
use the software settings, the corresponding
function's DIP switch code must be configured in
the outdoor units)
000: Auto Priority
001: Cool Priority
010: VIP
011: Heat Only
100: Cool Only
111: Set silent mode via the centralized controller
(To use the software settings, the corresponding
function's Dip switch code must be configured in
the outdoor units)
nb3: Exit auto power saving mode
nb4: Enter auto power saving mode
CCM-180A/WS
Grade 5
Grade 6
8
9
10
11
0
1
2
3
4
5
6
7
Auto Priority
Cool Priority
VIP
Heat Only
Cool Only
OFF
ON
41