Commissioning
7.5

Configuration of the inputs

7.5.1
Configuration of the HART inputs
Connecting and addressing HART devices
1
E
2
1
CDI
i
1
3
F
2
4
HR
on
WP
POWER
SIM
 29
Possible terminals for HART loops
B
Analog I/O module in slot B (availability depending on device version )
C
Analog I/O module in slot C (availability depending on device version )
E
HART Ex is output (available in all device versions)
HART devices must be configured and given a unique HART address via their own user
interface before they are connected to the Proservo NMS8x
Submenu: Setup → Advanced setup → Input/output → Analog I/O
Parameter
Meaning / Action
Operating mode Select:
• HART master+4..20mA input if only one HART device is connected to this loop. In this case the
4-20mA signal can be used in addition to the HART signal.
• HART master if up to 6 HART devices are connected to this loop.
3)
The current software does not support HART devices with address 0 (zero).