1. G
D
ENERAL
ESCRIPTION
The UZK12.071 battery module utilizes one non-
spillable maintenance-free VRLA lead-acid battery,
which is assembled in a package with all wiring and
fusing included.
The battery module is available in two different
options. It can be ordered as UZK-module with a battery
or as UZO-module without a battery which can be
installed at a later date to avoid outdated batteries.
The battery module can either be mounted on a DIN-rail
or be screwed on a flat surface.
3. O
N
RDER
UMBERS
Battery Module UZK12.071
UZO12.07
UZB12.071
Aug. 2017 / Rev. 2.2 DS-UZK12.071
All parameters are typical values specified at, 25°C ambient temperature unless otherwise noted.
Battery module with
assembled batteries
Battery module without
assembled batteries
Battery replacement
12V, 7Ah
www.pulspower.com Phone +49 89 9278 0
UZK12.071, UZO12.07
B
ATTERY
B
M
ATTERY
ODULE
Two Mounting Options:
DIN-Rail or Panel/ Wall Mounting
Small Mounting Footprint
Easy Access to the Terminals and the Fuse
Heavy Duty Fuse Holder and Spare Fuse Included
3 Year Warranty, Except for Batteries, Which Are
Considered a Service Part.
2. S
-
HORT
FORM
Nominal voltage
DC 12V
Nominal battery
7Ah
capacity
Nominal battery life
3 to 5 years
Battery current
Max. 30A
Max. 1.8A
Recommended
13.9V
charging voltage
13.75V
13.6V
13.45V
Self-discharge rate
3%/month
Battery fuse
30A
Temperature range
-10°C to +40°C
-15°C to +50°C
Size (WxHxD)
155x124x112mm WxHxD
Weight
3300g / 7.3lb
600g / 1.32lb
4. M
ARKINGS
Germany
M
12V, 7AH
ODULE
D
ATA
According EUROBAT
Discharging current
Charging current
At 10°C
At 20°C
At 30°C
At 40°C
At 20°C
®
ATOF
287 030 from
Littelfuse
For charging
For discharging
For UZK12.071
For UZO12.07
Marine
IECEx
Class I Div 2
ATEX
1/11

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Dimension U Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Puls Dimension U Series

  • Page 1: General Description

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE ATTERY ODULE Two Mounting Options: DIN-Rail or Panel/ Wall Mounting Small Mounting Footprint Easy Access to the Terminals and the Fuse Heavy Duty Fuse Holder and Spare Fuse Included 3 Year Warranty, Except for Batteries, Which Are Considered a Service Part.
  • Page 2: Table Of Contents

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE NDEX Page Page General Description ..........1 11. Environment ............6 Short-form Data ..........1 12. Terminals and Wiring......... 6 Order Numbers............1 13. Protection Features ..........7 Markings ..............1 14. Approvals ............7 Intended Use ............3 15.
  • Page 3: Intended Use

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE 5. I NTENDED This module is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment. Do not use this module in equipment, where malfunction may cause severe personal injury or threaten human life. 6.
  • Page 4: Hazardous Location Installation Instructions

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE Place the battery module in a cool area inside a cabinet. Install the device in an enclosure providing protection against electrical, mechanical and fire hazards. Ensure sufficient ventilation by following the requirements of the EN 50272-2. CAUTION: The unit contains wet cell batteries.
  • Page 5: Instructions For Replacing Batteries

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE 10. I NSTRUCTIONS FOR EPLACING ATTERIES Batteries need to be replaced periodically. The time interval depends on the ambient temperature in which the battery is used and on the number and depth of discharge cycles. In a typical application it is recommended to replace the batteries at least every 2 years.
  • Page 6: Terminals And Wiring

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE 11. E NVIRONMENT -10°C to +40°C (14°F to 104°F) For charging Operational temperature Frequently charging below +5°C (41°F) reduced the lifetime of the battery -15°C to +50°C (5°F to 122°F) For discharging -20°C to +50°C (-4°F to 122°F) For storage and transportation Storage temperature Recommendation:...
  • Page 7: Environment

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE 13. P ROTECTION EATURES Degree of protection IP 00 According to EN/IEC 60529 Class of protection According to EN/IEC 61140 Internal input fuse DC-Fuse (blade type) ATOF ® 287 030 from Littelfuse Replacement fuses must be of the same type or an UL listed fuse with the same nominal value and characteristics.
  • Page 8: Physical Dimensions And Weight

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE 16. P HYSICAL IMENSIONS AND EIGHT Width 155mm / 6.1’’ Height 124mm / 4.88’’ Depth 112mm / 4.41’’ For DIN-Rail mounting; The DIN-rail height must be added to the unit depth to calculate the total required installation depth. Weight 3300g / 7.3lb For UZK12.071...
  • Page 9: Wall/ Panel Mounting

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE 17. W ANEL OUNTING Panel/ wall mounting is possible by detaching the DIN-Rail brackets Fig. 17-1 Panel/ wall mounting – Removing the aluminium brackets and plastic slide Detach the two aluminum brackets Remove the plastic lock mechanism Panel/ wall mounting is possible by removing the two screws with a by using a flat-blade screwdriver to...
  • Page 10: Recommendations For A Long Battery Life

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE 18. R ECOMMENDATIONS FOR A ATTERY Temperature: The temperature has the most impact on the service life. The hotter the temperature, the earlier the wear-out phase of the battery begins. The wear-out results in a degradation of battery capacity. Place the battery module in a cool location, e.g.
  • Page 11: Mounting Orientations

    UZK12.071, UZO12.07 12V, 7AH U-Series ATTERY ODULE 19. M OUNTING RIENTATIONS The standard mounting orientation is the vertical installation onto a flat surface. Fig. 19-1 Standard mounting orientation The following mounting orientations are also allowed: Fig. 19-2 Allowed mounting orientations Do not use the battery module in an upside down position: Fig.

This manual is also suitable for:

Dimension uzk 12.07Dimension uzk 12.071

Table of Contents