Eaton PXS24 Series Technical Manual page 9

Hide thumbs Also See for PXS24 Series:
Table of Contents

Advertisement

PXS24... system
Mechanical:
Number of channels
4.1
Width
Height
Depth
Feed-in terminals (optional)
Output terminals
Terminal type
Terminal capacity of load
inputs and load outputs
Communication port
Terminal type of the
communication port
Terminal capacity of the
communication port
Busbar system
Assembly
Status LED
Slider
Remote signaling output
Trip indicator
Remote signaling input
On
Off
Reset
Sequence control
Text field
Degree of protection
Ambient temperature
Storage temperature
Humidity
1
17.5 (1 MU)
92.5 mm
119.2 mm
3 x LINE (+) and 3 x GND (-)
3 x LOAD (+) and 3 x GND (-)
Push-in terminals
0.5-2.5 mm² (flexible with ferrule)
0.5-4 mm² (rigid)
Not available
Not available
Not available
LINE (+) and GND (-); max. 80 A
Different lengths up to 1 m
Snap-fit onto a TH35 mounting rail (EN 60715)
Two-colored; green = OK;
red = tripped
Off = channel not in operation
On/off/reset
Not available
Not available
Not available
17.5 x 6 mm
IP20
-30 °C to 55 °C
-40 °C to 100 °C
96h/95% relative humidity at 40 °C as per IEC 600068-2-78 (non-
condensing)
Technical manual MD019003EN
Valid as of September 2020
2 x communication output (internally
linked)
2 x communication input (internally
linked)
1 x GND
Push-in terminals
1 mm² (flexible with ferrule)
1.5 mm² (rigid)
According to IEC 61131-2;
Max. current load 200 mA;
Max. 30 PXS24 units can be connected
simultaneously
According to IEC 61131-2;
Max. 30 PXS24 units can be connected
simultaneously
Via the communication port
EATON www.eaton.com 9