Intended Use; Reasonably Foreseeable Misuse; Determining The Lifetime And Validating The Entire System; Example Calculation - Captron safeCAP SC4 Original Operating Instructions

Table of Contents

Advertisement

2.4

Intended use

Combined with safety relay MCR-225, safeCAP SC4 ensures safety-
related release and interruption of a safety circuit. safeCAP SC4 is used to
protect people from work machines with dangerous closing movements. If
safeCAP SC4 is used without the aforementioned safety relay, the operator is
responsible for safety-related release and interruption of the safety circuit.
2.5

Reasonably foreseeable misuse

Any use other than as specified in the section
beyond this is deemed to be improper.
The switch is not suitable for:
use as a two-hand control without the aforementioned relay or independent
calculation of the performance level in accordance with ISO 13849.
use as a two-hand control without validation of the entire system.
use as an emergency stop command device.
use in potentially explosive atmospheres.
use outdoors.
2.6
Determining the lifetime and validating the
entire system
The following steps are mandatory.
Determine the real parameters of the system.
Required performance level
4
d
4
op
h
4
op
t
4
cycle
The operator must verify that the lifetime T
Validate the entire system.
Observe the safety considerations in the operating instructions of the safety
relay.
2.7

Example calculation

The following values are only examples and must be replaced with your own
values.
6/19
Intended use
is not exceeded.
M
1.3
or extending
safeCAP SC4
safeCAP SC4 with MCR-225

Advertisement

Table of Contents
loading

Table of Contents