Pulse duration connection test
Comment:
1
All values in combination with sensors approved by Siemens.
2
Numerical aperture (NA = sin θ (launch angle))
High-Speed Measuring-Transducer Inputs, Voltage/Current (via IO210, IO212)
NOTE
i
i
Current and voltage must not be connected at the same time to one measuring-transducer input. Instead,
only connect either current or voltage. For EMC reasons, do not connect a line to an unused input (current
or voltage).
Use shielded cables.
Table 12-1
Differential voltage input channels IO210: 4
Measuring range
Fault
Input impedance
Conversion principle
Insulation test voltage between the
channels
Insulation test voltage with respect
to ground/housing
Max. permissible voltage with
respect to ground on the meas-
uring inputs
Permissible overload
Measured-value repetition
Insulation class IO210
Insulation class IO212
Table 12-2
Differential current input channels
Measuring range
Fault
Input impedance, current
Conversion principle
Permissible potential difference
between channels
Galvanic separation with respect to
ground/housing
Permissible current overload
21
The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
22
The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
23
The IO210 has 4 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
24
The IO212 has 8 high-speed measuring-transducer inputs. They can be used either as a voltage or current input.
SIPROTEC 5, Paralleling Device, Manual
C53000-H5040-C071-1, Edition 05.2018
11 μs
High-Speed Measuring-Transducer Inputs, Voltage
IO212: 8
DC -10 V to +10 V
< 0.5 % of the measuring range
48 kΩ
Delta-sigma (16 bit)
DC 3.5 kV
DC 3.5 kV
300 V
DC 20 V continuously
DC 60 V continuously (IO210 MT3 terminal point C9)
62.5 μs
ELV (Extra Low Voltage) (acc. to IEC 60255-27)
SELV (acc. to IEC 60255-27)
High-Speed Measuring-Transducer Inputs, Current
IO210: 4
IO212: 8
DC -20 mA to +20 mA
< 0.5 % of the measuring range
12 Ω
Delta-sigma (16 bit)
DC 3.5 kV
DC 3.5 kV
DC 100 mA continuously
21
22
23
24
Technical Data
12.1 General Device Data
709