Tolerances for Stage Type Inverse-Time Undervoltage Protection
Voltages
Currents
Operate time for 0 < V/V
Reset time delay
SIPROTEC 5, Paralleling Device, Manual
C53000-H5040-C071-1, Edition 05.2018
< 0.9
Thresh
12.7 Undervoltage Protection with 3-Phase Voltage
0.5 % of the setting value or 0.05 V
1 % of the setting value or 5 mA (I
(I
= 5 A, f
± 10 %), valid for protection-class
rated
rated
current transformers
1 % of the setting value or 0.1 mA (I
0.5 mA (I
= 8 A, f
± 10 %), valid for instrument
rated
rated
transformers
5 % of the setting value or 30 ms
1 % of the setting value or 10 ms
Technical Data
= 1 A) or 25 mA
rated
= 1.6 A) or
rated
729