Technical Data
12.12 Vector-Jump Protection
12.12
Vector-Jump Protection
Setting Values
Threshold V1 min
Threshold V1 max
Threshold Δφ
Operate delay
T Reset
T Block
I< Threshold
Times
Pickup times
Dropout times
Frequency Operating Range
f
- 3 Hz ≤ f or f
rated
f < f
- 3 Hz or f > f
rated
Tolerances
Angle jump
Voltage blocking
Undercurrent release
Time delay T
61
OOT (Output Operating Time): additional delay of the output medium used. You can find more information in chapter
Outputs.
754
0.300 V to 175.000 V
0.300 V to 175.000 V
2.0° to 30.0°
0.00 s to 60.00 s
0.00 s to 60.00 s
0.00 s to 60.00 s
0.030 A to 35.000 A at 1 A
0.150 A to 175.000 A at 5 A
Approx. 80 ms + OOT
Approx. 66.8 ms + OOT at 60 Hz
Approx. 80 ms + OOT at 50 Hz
Approx. 66.8 ms + OOT at 60 Hz
≤ f
+ 3 Hz
According to specified tolerances
rated
rated
+ 3 Hz
Inactive
rated
0.5° at V > 0.5 V
1 % of the setting value or 0.500 V
For I
For I
1 % or 10 ms
61
at 50 Hz
rated
= 1 A: 1 % of the setting value or 10 mA
rated
= 5 A: 1 % of the setting value or 50 mA
rated
SIPROTEC 5, Paralleling Device, Manual
C53000-H5040-C071-1, Edition 05.2018
Increments of 0.001 V
Increments of 0.001 V
Increments of 0.1°
Increments of 0.01 s
Increments of 0.01 s
Increments of 0.01 s
Increments of 0.001 A