Reset Service Interval Counter - Rinnai E85SRN Installation & Servicing Instructions Manual

High efficiency condensing gas boiler
Table of Contents

Advertisement

9
8
Siphon
figure 35
13
14
12
11
Condensate tray
figure 36
!
DANGER
Clamping rods
figure 37
!
DANGER
!
WARNING
!
WARNING
64
Condensate trap and condensate tray (figure 35-37) (2 and 4 year maintenance)
Step 1: Condensate trap
-
First remove the screw (7);
-
Pull the condensation cup (8) downwards, out of the condensate tray (14)
Check this for impurities. If there is not a lot of impurities it is not necessary to
clean the condensate tray (Go to Step 3). If there is a lot of impurities in the cup
it is necessary to remove and clean the condensate tray according Step 2;
7
-
Check the O-ring (9) of the cup and replace if necessary;
- Clean the parts by flushing it with clean water;
- Grease the O-ring again with acid free O-ring grease to make fitting easier;
-
If there is a leak at the condensate trap (8) replace complete condensate trap by
# 809000100;
Step 2: Condensate tray
- Remove the plug from the flue gas sensor if present;
-
Turn the two short clamping rods (11 and 12) ¼ turn and remove them by pulling
them forward; Note the right turning direction (red indicator);
-
Lift the exhaust pipe (13) out of the condensate tray (14);
-
Press the condensate tray (14) carefully downwards and remove it by pulling it
forward;
-
Replace the gasket between condensate tray and heat exchanger with a new one;
-
Clean the condensate tray with water and a hard brush;
-
Check the condensate tray for leaks.
Step 3: Refitting is done in reverse order.
Note that all gaskets seals completely.
Make sure that during refitting the clamping rods they are put in the right
position. They should be turned vertical.
If the boiler should activate with clamping rods in the wrong position it will
cause property damage, personal injury or loss of life.
Put the boiler into operation and check the O
If replacement of new gaskets and burner mentioned in this chapter is not done
within the service interval subscribed by Rinnai the boiler can be damaged and
may cause property damage, personal injury or loss of life.
Use only original spare parts supplied by Rinnai. If non approved parts are used
the boiler can be damaged and may cause property damage, personal injury or
loss of life. Use of non-Rinnai parts will result in the voiding of the limited warranty.
Do not use substitute materials. Use only parts certified with the appliance.
(see chapter 14.3).
2

Advertisement

Table of Contents
loading

Table of Contents