External Accessories; Ul Listings And File Numbers - Siemens SBA 800 Information And Instruction Manual

Table of Contents

Advertisement

Ordering Information

External Accessories

Key Interlocks
Accessory
Installed on Breaker
Provision only
Circuit Breaker
Drawout
Padlock Devices
Accessory
Installed on Breaker
Installed on Drawout
Breaker Closing Blocking Device
Accessory
Breaker Closing Blocking Device
Capacitor Trip
Accessory
Capacitor Trip
Cell Switches
Accessory
1A & 1B
2A & 2B
3A & 3B
4A & 4B
Mechanical Interlock
Accessory
800A, 1200A Envelope
Fixed Circuit Breaker
Drawout Circuit Breaker
2000A Envelope
Fixed Circuit Breaker
Drawout Circuit Breaker
Electric Operator Troubleshooting Guide
Symptom
Motor does not run.
Motor runs for 20 seconds, does not charge
springs, lamp on LT4 blinks slowly (one
second on, two seconds off).
Breaker will not close electrically.
Lamp on LT4 blinks slowly (one second on,
two seconds off).
Courtesy of NationalSwitchgear.com
Catalog Number
KISB, SISB
KIPOF
SKIPOD, 20KIPOD
Catalog Number
SBPLB
SBPLD
Catalog Number
SBBD
Catalog Number
Consult Siemens
Catalog Number
CEL1
CEL2
CEL3
CEL4
Catalog Number
SBMIF08
SBMID08
SBMIF20
SBMID20
Solutions
1. Check for springs already charged by checking spring charge indicator.
2. Check for rated voltage at LT1 and LT5.
3. Check motor fuse - requires 1.8A Slo-Blo fuse.
4. Check all wiring connections.
5. If the lamp connected to LT4 is blinking slowly (one second on, two seconds off) remove power from LT1 and LT5 then
re-apply power
1. Remove power from LT1 and LT5, manually charge breaker. Reapply power to LT1 and LT5 motor should run for less than
10 seconds and shut off. Lamp on LT4 should remain on.
1. Check to see if springs are charged by checking charged indicator flag.
2. Check for power on LT1 and LT5.
3. Check for power on LT2. If power is on LT2, remove and reapply.
4. Check to see if breaker is locked in open position by either padlocking device, kirk key, or drawout interlock.
5. Check all wiring connections.
1. Remove power from LT1 and LT5, manually charge breaker springs. Reapply power to LT1 and LT5. Lamp on LT4 should
remain on.
Remote Indication Panel
Accessory
Catalog Number
Remote Indication Relay Panel
SBRIP
Display Module
Accessory
Catalog Number
Display Module
SBDM
Ground Fault Display Module
Accessory
Catalog Number
Ground Fault Display Module
SBGFM
Auxiliary Power Source For Electronic Trip
Unit
Accessory
Catalog Number
Auxiliary Power Source
SBAPM
Universal Trip Unit Test Kit
Accessory
Catalog Number
Test Kit
TS31

UL Listings and File Numbers

UL Listing
File Number
Trip Unit
E9896
Breaker
E9896
Draw Assembly
E135453
Accessories
E57501
CSA Guides
LR57039
Time Current Curves
Description
Catalog Number
Time Current Curves
TD7210
9 7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sba 2000Sba 1200Sba 400

Table of Contents