Internal Accessories
Electric Motor Operator
14.) Re-install the side plate mechanism assemblies if they
had been removed.
15.) Feed wires through wire opening in side panel as
illustrated above.
16.) Replace the trip unit by pushing it onto the plug. Slide the
trip unit over the bracket pins.
17.) Secure the unit by replacing the mounting screw Torque
screw to 6-8 in. lbs.
Courtesy of NationalSwitchgear.com
18.) Before replacing the breaker cover remove the fuse hole
plug from the inside of the cover as illustrated above.
Also cut out the "Fuse not installed" area of the rating
label.
19.) Replace front cover being careful not to pinch the wires
that are routed to the secondary disconnects or terminal
block.
20.) Replace the (4) #10 Phillips head screws at the corners
and the (4)1/4" Phillips head screws in recesses in cover.
45