Package Chiller Description - G&D VERTICAL AIR Series Installation Manual & User Manual

Table of Contents

Advertisement

INSTALLATION GUIDE • USER MANUAL
I

PACKAGE CHILLER DESCRIPTION

CONDENSER
– Standard configuration. Copper tube
AIR COOLED
aluminum fin vertical air flow condenser coil. Direct
drive propeller type fans with DDP motors and built-
in overload protection. Design test pressure 150 PSIG
low side, 300 high side.
LIQUID COOLED
– Optional configuration. Brazed
plate counterflow condenser with water regulation
valve. Shell and tube condensers available for custom
units.
EVAPORATOR
Brazed plate counterflow heat exchanger fed by
electronic expansion valve (EEV).
COMPRESSOR
Hermetically-sealed Frascold compressor with oil
level sight glass, rotalock service valves, and
crankcase heater.
PUMPS
End suction centrifugal pump with impeller trimmed
for 35% propylene glycol mixture. Base mounted.
Pump fitted with union, check valve, and supply and
return shut off valves for service. Variable frequency
drives available upon request.
RESERVOIR TANK
Constructed of molded, seamless high-density cross-
linked polyethylene or stainless steel. Insulated with
½" closed cell foam. Glycol level indicator. Auxiliary
ports standard on most units.
SUPPLY & RETURN PIPING
Constructed of type M copper. Flanges provided for
field connection of supply and return piping. Liquid-
filled pressure gauge for discharge pressure.
DYNAMIC FLUID BYPASS VALVE
Allows for balancing of discharge pressure. Over
pressure design allows circuiting back to tank without
damage to system or pump. Copper and bronze
construction.
G&D CHILLERS, INC.
 
GD-VA-R2022C
REFRIGERANT PIPING
Type L ACR copper. Liquid line-filter drier, sight
glass/moisture
indicator,
electronic expansion valve. Suction line fully insulated
and designed for proper oil return with minimum
friction loss. Discharge line formed of ACR tubing
reformed radius fittings. All piping leak tested and
evacuated. Ships with full operating charge of
refrigerant, refer to data plate for refrigerant type
and charge per circuit.
FRAME & HOUSING
Fully powder coated steel frame. Durable powder
coated aluminum housing rated for outdoor use.
Access panels for easy service and maintenance.
POWER & CONTROLS
A single-point electrical connection is provided for
terminating the chiller power wiring. All power
starting controls and safety/operating controls are
mounted in a weatherproof steel NEMA 3R enclosure.
Features include:
Programmable logic controller (PLC)
On / pump down / off door switch
Compressor contactor and circuit breaker
Pump contactor and circuit breaker
Pressure-based mechanical safeties
Flow switch interlock
Freeze protection interlock
High temperature alarm
Low ambient control
Compressor anti short cycle timer
Variable speed drives (VFD)
Water regulating valve (water cooled units)
FACTORY TESTING
All chillers are run tested at the factory and verified
to be in perfect working order prior to shipment.