REFRIGERANT PIPING
The compressor suction and discharge lines are copper. In  most instances, piping  may be reused. If piping  is not 
reusable, order the correct service parts. Cut all tubing with a tubing cutter to prevent copper filings from entering 
the system. Cut the tubing in a straight length of pipe after the compressor connection has been un‐sweated. The 
line can then be reinstalled using a slip coupling and brazing. 
NOTICE: The compressor suction line configuration must not be changed in any way. Changing compressor suction 
line configuration will compromise proper oil return to the compressor(s). 
COMPRESSOR ELECTRICAL TERMINAL BOX
Be  sure  to  protect  the  terminal  box  and  all  wiring  when  un‐brazing  or  brazing  compressor  refrigerant  piping 
connections 

COMPRESSOR REPLACEMENT

If the chiller suffers a failed compressor, use these steps for replacement: 
Each compressor has lifting eyes. Use proper lifting techniques. 
After a mechanical failure of a compressor, it is necessary replace the liquid line filter drier. After an electrical failure 
of a compressor, it will also be necessary to replace the liquid line filter drier and add a suction filter drier with clean‐
up cores. 
Note: Do not alter the refrigerant piping in any way as this can affect compressor lubrication. 
Note: Do not add a filter drier within 16 inches of the elbow of any compressor 25hp or larger. 
26