Digital Inputs - Emerson Dixell XRi77CX Installing And Operating Instructions

Digital controller for variable speed drive
Hide thumbs Also See for Dixell XRi77CX:
Table of Contents

Advertisement

ALL
Minimum temperature alarm:
If ALC=Ab: [-100°C to ALU; -148 to ALU];
If ALC=rE: [0.0 to 50.0°C or 0 to 90°F] when this temperature is reached the alarm is
enabled, after the Ald delay time.
AFH
Differential for temperature alarm recovery: (0.1 to 25.5°C; 1 to 45°F) intervention
differential for recovery of temperature alarm.
ALd
Temperature alarm delay: (0 to 255 min) time interval between the detection of an
alarm condition and alarm signalling.
dAo
Temperature alarm delay after power-on: (0.0 to 24h00min, res. 10min) time interval
between the detection of the temperature alarm condition after instrument power on
and alarm signalling.
CONDENSER TEMPERATURE ALARM
AP2
Second temperature alarm probe selection: (nP; P1; P2; P3; P4)
nP = no probe; P1 = thermostat probe; P2 = evaporator probe; P3 = configurable probe;
P4 = Probe on Hot Key plug.
AL2
Second low temperature alarm (absolute value): (-100 to 150°C; -148 to 302°F)
when this temperature is reached the LA2 alarm is signalled, possibly after the Ad2
delay.
Au2
Second high temperature alarm (absolute value): (-100 to 150°C; -148 to 302°F)
when this temperature is reached the HA2 alarm is signalled, possibly after the Ad2
delay.
AH2
Differential for second temperature alarm recovery: 0.1 to 25.5°C; 1 to 45°F
Ad2
Second temperature alarm delay: (0 to 255 min) time interval between the detection
of the condenser alarm condition and alarm signalling.
dA2
Second temperature alarm activation delay after power-on: 0.0 to 24h00min, res.
10min.
bLL
Compressor off due to second low temperature alarm: (n; Y) n = compressor keeps
on working; Y = compressor is switched off till the alarm is present, in any case
regulation restarts after AC time at minimum.
AC2
Compressor off due to second high temperature alarm: (n; Y) n = compressor
keeps on working; Y = compressor is switched off till the alarm is present, in any case
regulation restarts after AC time at minimum.
SAF
Differential for anti-freezing control: (0.0 to 25.5°C; 1 to 45°F) low level threshold to
stop regulation.
CONFIGURABLE RELAYS
oA1
Relay oA1 configuration (7-8): (dEF; Fan; Alr; LiG; AUS; onF; db; CP2; dEF2; HES;
Het; inV, CMP, nu) dEF = defrost; Fan = do not select it; Alr = alarm; LiG = light; AUS
= Auxiliary relay; onF = always on with instrument on; db = neutral zone; CP2 = second
compressor output; dF2 = do not select it; HES = night blind; Het = heater output; inV
= inverter compressor; CMP = ONOFF compressor; nu=not used.
oA2
Relay oA2 configuration (4-5-6): (dEF; Fan; Alr; LiG; AUS; onF; db; CP2; dEF2; HES;
Het; inV, CMP, nu) dEF = defrost; Fan = do not select it; Alr = alarm; LiG = light; AUS
= Auxiliary relay; onF = always on with instrument on; db = neutral zone; CP2 = second
compressor output; dF2 = do not select it; HES = night blind; Het = heater output; inV
= inverter compressor; CMP = ONOFF compressor; nu=not used.
oA3
Relay oA3 configuration (8-9): (dEF; Fan; Alr; LiG; AUS; onF; db; CP2; dEF2; HES;
Het; inV, CMP, nu) dEF = defrost; Fan = do not select it; Alr = alarm; LiG = light; AUS
= Auxiliary relay; onF = always on with instrument on; db = neutral zone; CP2 = second
compressor output; dF2 = do not select it; HES = night blind; Het = heater output; inV
= inverter compressor; CMP = ONOFF compressor; nu=not used.
oA4
Relay oA4 configuration (10-11-12): (dEF; Fan; Alr; LiG; AUS; onF; db; CP2; dEF2;
HES; Het; inV, CMP, nu) dEF = defrost; Fan = do not select it; Alr = alarm; LiG = light;
AUS = Auxiliary relay; onF = always on with instrument on; db = neutral zone; CP2 =
second compressor output; dF2 = do not select it; HES = night blind; Het = heater
output; inV = inverter compressor; CMP = ONOFF compressor; nu=not used.
oAn
Analogue output configuration: (n;Y) n = 5-pin port is used for HOT-KEY; Y = 5-pin
port is used as frequency output.
AoP
Alarm relay polarity: (oP; CL) oP = the relay is activated by opening the contact; CL
= the relay is activated by closing the contact.

DIGITAL INPUTS

i1P
Digital input 1 polarity: (oP; CL) oP = the digital input is activated by opening the
contact; CL = the digital input is activated by closing the contact.
i1F
Digital input 1 configuration: (EAL; bAL; dor; dEF; ES; AUS; Htr; HdF; onF; nt) EAL
= external alarm: "EA" message is displayed; bAL = serious alarm "CA" message is
displayed; dor = door switch function; dEF = activation of a defrost cycle; ES = energy
saving; AUS = auxiliary relay activation with oAx=AUS; Htr = type of inverting action
(cooling or heating); HdF =do not set it; onF = to switch the controller off; nt = to change
parameter map
i2P
Digital input 2 input polarity: (oP; CL) oP = the digital input is activated by opening
the contact; CL = the digital input is activated by closing the contact.
i2F
Digital input 2 configuration: (EAL; bAL; dor; dEF; ES; AUS; Htr; HdF; onF; nt) EAL
= external alarm: "EA" message is displayed; bAL = serious alarm "CA" message is
displayed; dor = door switch function; dEF = activation of a defrost cycle; ES = energy
saving; AUS = auxiliary relay activation with oAx=AUS; Htr = type of inverting action
(cooling or heating); HdF =do not set it; onF = to switch the controller off; nt = to change
parameter map
did
Digital input 1 alarm delay: (0 to 255 min) delay between the detection of the external
alarm condition and its signalling.
When i1F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
d2d
Digital input 2 alarm delay: (0 to 255 min) delay between the detection of the external
alarm condition and its signalling.
When i1F= PAL, it is the interval of time to calculate the number of pressure switch
activation.
nPS
Number of pressure alarm events before stopping the regulation (Lock alarm):
(1 to 15) after nPS activations of the ixF=BAL digital input the regulation will be stopped.
odC
Compressor and fan status after door opening: (no; Fan; CPr; F_C) no = normal;
Fan = normal; CPr = compressor OFF, F_C = compressor OFF.
1592020670 XRi77CX-CH GB r1.1 15.10.2019
rrd
Regulation restart after open door alarm: (n; Y) n = outputs follow the odC
parameter. Y = outputs restart with a door open alarm.
HES
Differential for energy saving mode: (-30.0 to 30.0°C; -54 to 54°F) it sets the
increasing value of the set point [SET+HES] during the Energy Saving cycle.
LdE
Energy saving mode controls the lights (lights off when energy saving goes
active): (n, Y) n= lights are independent from energy saving; Y = lights are turned OFF
when energy saving mode is activated
CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC)
Hur
Hours: 0 to 23h
Min
Minutes: 0 to 59min
dAY
Day of the week: Sun to Sat
dYM
Day of the month: 1 to 31
Mon
Month: 1 to 12
YAr
Year: 0 to 99
Hd1
First day of weekend: (Sun to Sat; nu) set the first day of the week which follows the
holiday times.
Hd2
Second day of weekend: (Sun to Sat; nu) set the second day of the week which
follows the holiday times.
N.B.
Hd1, Hd2 can be set also as "nu" value (Not Used).
ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC)
iLE
Working days Energy saving starting time: (0 to 23h50min) during the Energy
Saving cycle the set point is increased by the value in HES so that the operation set
point is SET+HES.
dLE
Working days Energy saving duration: (0 to 24h00min) sets the duration of the
Energy Saving cycle on workdays.
iSE
Holyday Energy saving starting time: 0 to 23h50min.
dSE
Holyday Energy saving duration: 0 to 24h00min.
DEFROST TIMES (ONLY FOR MODELS WITH RTC)
dd1...dd6
Daily defrost: (n; Y) to enable the Ld1...Ld6 defrost operations for all the days
of the week.
Ld1...Ld6
Defrost starting time: (0 to 23h50min) these parameters set the beginning of
the 6 programmable defrost cycles during workdays. Ex: when Ld2=12.4 the
second defrost starts every Monday at 12.40.
N.B.: To disable a defrost cycle set it to "nu"(not used). Ex: if Ld6=nu; the sixth defrost cycle will
be disabled.
OTHER
Adr
Serial address: (1 to 247) identifies the instrument address when connected to a
ModBUS compatible monitoring system.
onC
ONOFF button configuration: (nu; oFF; ES) nu=not used; oFF=to switch OFF and
ON the controller; ES=to enable and disable enersy saving mode
on2
ONOFF button timed (3sec) configuration: (nu; oFF; ES) nu=not used; oFF=to
switch OFF and ON the controller; ES=to enable and disable enersy saving mode
LG2
Light button timed (3sec) configuration (left upper side): (nu; LiG; AUS; Lnt)
nu=not used; LiG= to activate and deactivate light output; AUS=to activate and
deactivate the auxiliary output; Lnt=to change parameter map
dn2
Down button timed (3sec) configuration: (nu; Std; Lnt; Pnd) nu=not used;
Std=standard use; Lnt= to change parameter map; Pdn=to activate a Pull Down cycle.
dP1
Probe P1 value visualization: read only
dP2
Probe P2 value visualization: read only
dP3
Probe P3 value visualization: read only
dP4
Probe P4 value visualization: read only
SPd
Instantaneous Variable Speed Drive speed (in percentage): read only
rSE
Real set point: it shows the set point used during the energy saving cycle or during
the continuous cycle.
rEL
Firmware release for internal use.
Ptb
Parameter table code: readable only.
14. DIGITAL INPUTS
The first digital input (terminals 18-20) is enabled with P3P=n.
With P3P=n and i1F=i2F the second digital input is disabled.
The free voltage digital inputs are programmable by the i1F and i2F parameters.
14.1 GENERIC ALARM (IXF = EAL)
As soon as the digital input is activated the unit will wait for did time delay before signalling the "EAL"
alarm message. The outputs status doesn't change. The alarm stops just after the digital input is de-
activated.
14.2 SERIOUS ALARM MODE (IXF = BAL)
When the digital input is activated, the unit will wait for did delay before signalling the "CA" alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
14.3 DOOR SWITCH INPUT (IXF = DOR)
It signals the door status and the corresponding relay output status through the odC parameter:
no = normal (any change); FAn = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter doA, the door alarm is enabled,
the display shows the message dA and the regulation restarts is rtr=Y. The alarm stops as soon as
the external digital input is disabled again. With the door open, the high and low temperature alarms
are disabled.
14.4 START DEFROST (IXF = DEF)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will
restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is
expired.
XRi77CX-CH
5/9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dixell xri77ch

Table of Contents