„ Secure the electrical wiring with cable ties as shown
in the figure in 10.2 .
„ Make sure no external pressure is applied to the
terminal connectors.
„ When installing the earth leakage circuit breaker make
sure that it is compatible with the inverter (resistant to
high frequency electrical noise ) to avoid unnecessary
opening ofthe earth leakage circuit breaker.
„ As this unit is equipped with an inverter, installing a
phase advancing capacitor not only will deteriorate
power factor improvement effect, but also may cause
capacitor abnormal heating accident due to high-
frequency waves. Therefore, never install a phase
advancing capacitor.
CAUTION
Be sure to install the required fuses or circuit
breakers.
10.2. Connecting power supply and inter-
unit wiring
„ Connect and fix the power supply cable, indoor-
outdoor connection cable as following:
Power supply:
380-415V,3N~,
50/60Hz
For three phase power supply models:
1U105S2SS1FB 1U125S2SN1/2FB 1U140S2SN1FB
1U140S2SP1/2FB 1U160S2SP1FB
Power supply cable:
2
H05RN-F 5G 4mm
,
Indoor and outdoor connection cable:
2
H05RN-F 4G 2.5mm
£n-
outdoor unit connection cable length L satisfied
condition 40m< L<55m, please change the connection
cables specification to H07RN-F 4G 4.0mm
indoor and outdoor unit connection cable length L
satisfied condition 55m< L1<75m, please change the
connection cables specification to H07RN-F 4G 6.0mm
£'
Outdoor unit
terminal blocks
1U105S2SS1FB
1U125S2SN1/2FB
1U140S2SN1FB
1U140S2SP1/2FB
1U160S2SP1FB
Indoor unit
terminal blocks
1
Note
Ifthe indoor and
£"
2
. If the
Power supply:
1PH,220-240V~,
50/60Hz
For single phase power supply models:
1U105S2SS1FA,1U105S2SS2FA,
Power supply cable: H05RN-F 3G 4.0mm
1U125S2SN1FA,1U125S2SN2FA,1U140S2SP2FA,
1U140S2SN1FA,1U140S2SP1FA
Power supply cable: H05RN-F 3G 6.0mm
Indoor and outdoor connection cable: H05RN-F 4G 2.5mm
1
£n-
Note£" If the indoor and outdoor unit connection
cable length L satisfied condition 40m< L<55m, please
change the connection cables specification to H07RN-F
2
4G 4.0mm
. If the indoor and outdoor unit connection
cable length L satisfied condition 55m<L<75m, please
change the connection cables specification to H07RN-F
2
4G 6.0mm
£'
„ Fix the cable with the clip to prevent slide.
Clip
Outdoor-indoor unit
connection cable
„ Secure the cable to the stop valve attachment plate
so that it does not slide.
„ When cables are routed from the unit, a protection
sleeve for the conduits (PG-insertions) can be
inserted at the knock-out hole.
„ When you do not use a wire conduit, be sure to
protect the wires with vinyl tubes to revent the edge of
the knock-out hole from cutting the wires.
„ Follow the electric wiring diagram for electrical wiring
2
works.
20
Outdoor unit
terminal blocks
1U105S2SS1/2FA
1U125S2SN1/2FA
1U140S2SN1FA
1U140S2SP1/2FA
Indoor unit
terminal blocks
2
2
Clip
Power supply cable