Installation method (continued)
3. When interlocking with a pulse output
device
(1) Move the pulse input switch [SW2-2] to the ON position.
On the LGH-F1200RX
3
boards the same.
(2) Connect the pulse output device (i.e., building management sys-
tem) to the external control input terminal block [TM2].
The LGH-F1200RX
-E connected to the lower circuit board. (Main
3
circuit board)
•
A pulse width of at least 200 msec will be needed.
(3) Wiring is to be performed in the same way as for item 2 above.
1
2
3
4
5
6
7
8
SW2
ON
OFF
4 . When operating multiple Lossnay units
(1) Connect from Lossnay Unit 1 to Lossnay Unit 2, and from Unit 2
to Unit 3 and so on up to a maximum of 15 units (7 units for types
F1200) using a transmission cable (PVC insulated PVC jack-
eted and either between φ 1/32" and φ 3/64", or between AWG22
and AWG17 in cross section).
(2) Change the setting on the main/sub switch (SW1) on the second
and subsequent Lossnay units to "sub".
Lossnay
(Main)
Remote controller (PZ-41SLB-E)
Power
External
supply
device
Lossnay (Sub)
Power
supply
Lossnay (Sub)
Power
supply
LGH-F300, F600RX
-E
3
MAX 15 units
LGH-F1200RX
-E
3
MAX 7 units
Transmission cable
(The upper control circuit for LGH-F1200RX
NOTE
Up to four AWG22 stranded wires or φ 3/64" PVC wires can
•
be connected to one input terminal.
•
For other types of wire up to two can be connected.
•
The operation signal and pulse signal can be connected to
the external device of the main Lossnay only.
•
Connect the power to each respective Lossnay unit.
5. When switching high/low speed externally
(when CO
sensor or other device is
2
connected)
If a commercially available CO
as shown in the drawing, connect by inserting Remote ON/OFF
Adaptor (PAC-SE55RA-E) (sold separately) to the CN16 connector
(for switching between high/low).
*
The LGH-F1200RX
-E is connected to the lower circuit board.
3
(Main circuit board)
*
Note that if the remote controller is connected to a CO
the actual high and low fan speeds may not match on the remote
controller.
-E, set both the upper and lower circuit
Power supply
Operating switch
for external device
Main/Sub selection switch
(SW1)
Main Sub
First Lossnay
Connect to remote
5
6
controller
(PZ-41SLB-E)
Second
5
6
Lossnay
Connect to third
Lossnay
-E is normally set to "Sub".)
3
sensor or other such device is used
2
I To force high speed externally
When external switch is "on" fan speed of the Lossnay will be set
to "high".
Regardless of the remote control setting.
CO
sensor, etc.
2
(Closed when there is
an increase in CO
Switch
Switch: High operation
switch (When closed, high
operation)
I To force low speed externally
When external switch is "on" fan speed of the Lossnay will be set
to "low".
Regardless of the remote control setting.
CO
sensor, etc.
2
(Closed when there is
a decrease in CO
Switch
Switch: Low operation
switch (When closed, low
operation)
6. When connecting to the City Multi or
Mitsubishi Electric Air-Conditioner Network
System (MELANS)
*
If centralized control is performed according the wire connection
shown in this section, the remote controller (PZ-41SLB-E) can-
not be used.
Round terminal
M-NET transmission cable
•
One shieled wire is connected to the other shieled wire.
(Terminal connection)
Address setting is required. (Refer to function setting section.)
M-NET transmission cable: Connect any of the following -- City
Type: (Shielded wire, CVVS/CPEVS)
Wire diameter: AWG16 to AWG14
Securely connect the M-NET transmission cable to A and B on
•
the transmission cable input terminal block (TB5). (No-Polar)
sensor,
2
Remote ON/OFF Adaptor
(sold separately PAC-
)
SE55RA-E)
2
Orange 1
Red 2
Brown 3
Not used. Insulate
completely.
Wiring length up to a maximum of
32 ft
Remote ON/OFF Adaptor
(sold separately PAC-
)
SE55RA-E)
2
Orange 1
Red 2
Brown 3
Not used. Insulate
completely.
Wiring length up to a maximum of
32 ft
M-NET transmission cable input terminal block
LGH-F300, F470,
F600RX
-E
LGH-F1200RX
3
TB5
TB5
A B S
5
6
A
Shielded wire
Multi indoor unit or Mitsubishi Electric
Air-Conditioner Network System
(MELANS) - to the Lossnay.
Lossnay controller
circuit board
CN16
High/low
switching
Lossnay controller
circuit board
CN16
High/low
switching
-E
3
B S
9