INTERFACES
The assembly interfaces to the multi-party cable and the external loudspeaker via P1, the 16-pin
connector, and connector J1. The pin functions for connector P1 are described below:
Pin No.
Function
1
PL_L1
2
PG_L1
MT_L1
3
4
N/C
5
SPKR_8
SPKR_16
6
N/C
7
8
AC_N

Installation

Before installing Page/Party™ equipment, design the system layout taking into consideration personnel
safety, operational function, convenience, and power cable length. System cable length (power
conductors) requirements for 115 V ac systems must be calculated by determining the overall voltage
loss due to cable resistance and individual station voltage drops. The end of line station requires a
minimum operating voltage of 90 V ac.
A separate power feed is recommended to each station located in hazardous areas. With a separate feed,
individual stations can be de-energized for service or maintenance without affecting the power supply
and operation of the other stations in the hazardous area.
8/98
k:\standard ioms - current release\instr. manuals (42004)\42004-305.doc
™ S
A
PEAKER
MPLIFIER
Description
Party line (L1)
Page line (L1)
Mute (L1)
No connection
Speaker (8-ohm)
Speaker (16-ohm)
No connection
AC neutral
Figure 5. Mounting holes with dimensions in inches (mm)
Pin No.
Function
9
PL_L2
10
PG_L2
MT_L2
11
12
N/C
13
EGND
SPKR_C
14
N/C
15
16
AC_H
PAGE: 4 OF 10
PUB.: 42004-305
Description
Party line (L2)
Page line (L2)
Mute (L2)
No connection
Earth ground
Speaker (common)
No connection
AC hot
Level 2
Rev: 0