4.4 Water quality
Lindab recommend water treatment and quality to be according to VDI 2035-2.
The water preparation and maintenance for the chilled beam water circuit should be
handled by a specialist
To prevent corrosion, the water circuit must be airtight
The water system must also be equipped with aerators to remove any build-up air in
the system.
The water should be oxygen free, to prevent corrosion.
The water system must be filled with potable water that complies with the EC direc-
tive 98/83/EC.
pH value of water must be between approximately 6-9 pH
The water velocities should not exceed 1m/s, and should be kept as close to the
nominal flow as possible to minimize noise and optimize the energy yield
There should be used in-line strainers to remove dirt particles from the water.
If the water contains any additive inhibitor this must be appropriate to use with copper
and solder.
4.5 Air quality
Primary supply air should be clean and filtered before reaching the beam.
4.6 Capacity test
Lindabs active chilled beams are Eurovent-certified and tested according to
EN-15116.