Summary of Contents for Lindab Celo

  • Page 1 | we sim pli fy c onst ruc tion Celo Service & maintenance © 04.2020 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).
  • Page 2: Installation

    1.0 Installation 1.1 Product description Lindab has developed a active chilled beam, Celo, which can be installed above a suspended ceiling. Thus, you can conceal the ventilation and cooling features and create an unbroken ceiling without visible technical installations. The Celo con- cept has been developed together with Ecophon, which provides acoustic ceilings adapted for the system.
  • Page 3 Mount a push-on fitting to the pipe. Make sure to press the fitting all the way onto the pipe. Consult the installation guide for the specific fitting for further details on proper installation. Push-on fitting Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 4 Crocked or in other ways imperfect pipe ends will result in leaks. Deburr the pipe on the inside and the outside, using a deburr- ing tool before installation Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 5 – Both flow and return pipe is covered by a plastic or rubber protection cover, which should be removed before installation. Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 6 Push-on fitting Push-on valve Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes. Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 7 2.2.1 Measure the static nozzle pressure. – To measure the air pressure, a manometer, analog or digital (such as the Lindab PC410) will be needed. – Insert the measuring tube onto the specialized measuring nozzle –...
  • Page 8 – Plug or unplug nozzles to reach the desired air flow. – Dividing the plugs evenly, will result in an even air spread. Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 9: Maintenance

    Celo 3.0 Maintenance The interval of cleaning depends on the indoor environment where the beam is placed. Under optimal conditions the Celo beams only need cleaning every 5 years. 3.1 Cleaning instructions – Clean underneath the battery with a vacuum cleaner and a piece of wet cloth –...
  • Page 10 This means the maximal working pressure for the products at a water temperature of 20°C must not exceed 10 bar. 4.4 Water quality Lindab recommend water treatment and quality to be according to VDI 2035-2. – The water preparation and maintenance for the chilled beam water circuit should be handled by a specialist –...
  • Page 11 4.5 Air quality – Primary supply air should be clean and filtered before reaching the beam. 4.6 Capacity test – Lindabs active chilled beams are Eurovent-certified and tested according to EN-15116. Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 12 Änderungen vorbehalten. IT - Qui potete trovare istruzioni di montaggio, informa- zioni sul prodotto ed un supporto tecnico qualificato Tel. 011 9952099 - e-mail: lindab@lindab.it www.lindab.it Soggetto a modifica senza obbligo di preavviso. FR - Vous trouverez les fiches produits ou de montage actualisées ainsi que les coordonnées du support télépho-...