Download Print this page

Refrigerant Piping Work - Mitsubishi Electric Mr.Slim SUY-SM13VA-TH Installation Manual

Advertisement

Available languages

Available languages

4. Refrigerant piping work

A
(B)
(C)
Fig. 4-1
A
ø12.7
ø15.88
Fig. 4-2
b
a
90°
Fig. 4-3
b
a
c
Fig. 4-4
Fig. 4-5
a
A
b
c
Fig. 4-6
(A)
Indoor unit
A
Outdoor unit
B
B
Indoor unit
A
Outdoor unit
B
ø6.35
ø9.52
B
Copper tubes
a
Good
b
c
No good
c
d
e
f
Tilted
d
Uneven
e
Burred
f
Burr
a
Copper tube/pipe
b
Spare reamer
c
d
Pipe cutter
d
a
Flare nut
a
Copper tube
b
b
Flaring tool
a
e
Die
b
Copper tube
c
b
Flare nut
d
d
Yoke
e
c
4.1. Refrigerant pipe (Fig. 4-1)
► Check that the difference between the heights of the indoor and outdoor
units, the length of refrigerant pipe, and the number of bends in the pipe are
within the limits shown below.
(A) Pipe length
Models
(one way)
SUY-SM13/SM18
Max. 20 m
SUY-SM24/SM30
Max. 30 m
• Height difference limitations are binding regardless of which unit, indoor or out-
door, is positioned higher.
• Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant (R32)
charge is required.
(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)
Up to 7 m
No additional charge is required.
Pipe length
Additional charge is required.
Exceeding 7 m
(Refer to the table below.)
SUY-SM13/SM18 10 g × (refrigerant piping length (m) -7)
Refrigerant
SUY-SM24
20 g × (refrigerant piping length (m) -7)
to be added
SUY-SM30
20 g × (refrigerant piping length (m) -7)
Piping preparation
• Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.
(1) Table below shows the specifications of pipes commercially available.
Outside diameter
Model
Pipe
mm
For liquid
6.35
SUY-SM13
For gas
12.7
For liquid
6.35
SUY-SM18
For gas
12.7
For liquid
9.52
SUY-SM24
For gas
15.88
For liquid
9.52
SUY-SM30
For gas
15.88
(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
(3) Refrigerant pipe bending radius must be 100 mm or more.
Caution:
Using careful insulation of specified thickness. Excessive thickness prevents
storage behind the indoor unit and smaller thickness causes dew drippage.
• Be sure to have appropriate ventilation in order to prevent ignition. Further more,
be sure to carry out fire prevention measures that there are no dangerous or flam-
mable objects in the surrounding area.
• R32 maintenance refilling: Before servicing refilling the equipment with R32 to en-
sure that there is no risk of explosion from electrical sparks it must be ensured that
the equipment machine is 100% disconnected from the mains supply.
4.2. Flaring work
• Main cause of gas leakage is defect in flaring work.
Carry out correct flaring work in the following procedure.
4.2.1. Pipe cutting (Fig. 4-3)
• Using a pipe cutter cut the copper tube correctly.
4.2.2. Burrs removal (Fig. 4-4)
• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in
order to avoid burrs drop in the tubing.
4.2.3. Putting nut on (Fig. 4-5)
• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after flaring work)
4.2.4. Flaring work (Fig. 4-6)
• Carry out flaring work using flaring tool as shown at the right.
Pipe diameter
A (mm)
When the tool for R32 is used
(mm)
Clutch type
6.35
0 - 0.5
9.52
0 - 0.5
12.7
0 - 0.5
15.88
0 - 0.5
Firmly hold copper tube in a die in the dimension shown in the table at above.
(B) Height
(C) Number of
difference
bends (one way)
Max. 12 m
Max. of 10
Max. 15 m
Max. of 10
Maximum
amount of
refrigerant
0.98 kg
1.41 kg
1.52 kg
Min. wall
Insulation
Insulation
thickness
thickness
material
inch
1/4
0.8 mm
8 mm
1/2
0.8 mm
8 mm
1/4
0.8 mm
8 mm
Heat resisting
1/2
0.8 mm
8 mm
foam plastic
0.045 specific
3/8
0.8 mm
8 mm
gravity
5/8
1.0 mm
8 mm
3/8
0.8 mm
8 mm
5/8
1.0 mm
8 mm
Dimension
+0
(mm)
B
-0.4
9.1
13.2
16.6
19.7
7

Hide quick links:

Advertisement

loading