Refrigerant Piping Work - Mitsubishi Electric Mr.SLIM SUZ-KA71VA Installation Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

5. Refrigerant piping work

A
(B)
Fig. 5-1
A
ø9.52
ø12.7
ø15.88
Fig. 5-2
b
a
90°
Fig. 5-3
b
a
c
d
Fig. 5-4
Fig. 5-5
a
A
d
b
c
Fig. 5-6
4
(A)
A Indoor unit
B Outdoor unit
B
(C)
A Indoor unit
B Outdoor unit
ø6.35
ø9.52
B
a Copper tubes
c
b Good
c No good
d
e
f
d Tilted
e Uneven
f Burred
a Burr
b Copper tube/pipe
c Spare reamer
d Pipe cutter
a Flare nut
a
b Copper tube
b
a Flaring tool
b Die
e
c Copper tube
d Flare nut
b
e Yoke
c
5.1. Refrigerant pipe (Fig. 5-1)
s Check that the difference between the heights of the indoor and outdoor
units, the length of refrigerant pipe, and the number of bends in the pipe are
within the limits shown below.
Models
(A) Pipe length
(one way)
SUZ-KA25/KA35
max. 20 m
SUZ-KA50/KA60/KA71
max. 30 m
• Height difference limitations are binding regardless of which unit, indoor or outdoor,
is positioned higher.
• Refrigerant adjustment ... If pipe length exceeds 7 m, additional refrigerant (R410A)
charge is required.
(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)
Up to 7 m
Pipe length
Exceeding 7 m
SUZ-KA25/KA35 type 30 g × (refrigerant piping length (m) -5)
Refrigerant to be
SUZ-KA50/KA60 type 20 g × (refrigerant piping length (m) -7)
added
SUZ-KA71 type
Piping preparation
• Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.
(1) Table below shows the specifications of pipes commercially available.
Outside diameter
Model
Pipe
mm
inch
For liquid
6.35
1/4
SUZ-KA25
For gas
9.52
3/8
For liquid
6.35
1/4
SUZ-KA35
For gas
9.52
3/8
For liquid
6.35
1/4
SUZ-KA50
For gas
12.7
1/2
For liquid
6.35
1/4
SUZ-KA60
For gas
15.88
5/8
For liquid
9.52
3/8
SUZ-KA71
For gas
15.88
5/8
(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
(3) Refrigerant pipe bending radius must be 100 mm or more.
Caution:
Using careful insulation of specified thickness. Excessive thickness prevents
storage behind the indoor unit and smaller thickness causes dew drippage.
5.2. Flaring work
• Main cause of gas leakage is defect in flaring work.
Carry out correct flaring work in the following procedure.
5.2.1. Pipe cutting (Fig. 5-3)
• Using a pipe cutter cut the copper tube correctly.
5.2.2. Burrs removal (Fig. 5-4)
• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in
order to avoid burrs drop in the tubing.
5.2.3. Putting nut on (Fig. 5-5)
• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after flaring work)
5.2.4. Flaring work (Fig. 5-6)
• Carry out flaring work using flaring tool as shown at the right.
Pipe diameter
A (mm)
(mm)
When the tool for R410A is used
Clutch type
6.35
0 - 0.5
9.52
0 - 0.5
12.7
0 - 0.5
15.88
0 - 0.5
Firmly hold copper tube in a die in the dimension shown in the table at above.
(B) Height
(C) Number of
difference
bends (one way)
max. 12 m
max. of 10
max. 30 m *(15 m)
max. of 10
*(
): MFZ
No additional charge is required.
Additional charge is required.
(Refer to the table below.)
55 g × (refrigerant piping length (m) -7)
Min. wall
Insulation
Insulation
thickness
thickness
material
0.8 mm
8 mm
0.8 mm
8 mm
0.8 mm
8 mm
0.8 mm
8 mm
Heat resisting
0.8 mm
8 mm
foam plastic
0.8 mm
8 mm
0.045 specific
gravity
0.8 mm
8 mm
0.8 mm
8 mm
0.8 mm
8 mm
1.0 mm
8 mm
Dimension
+0
B
(mm)
-0.4
9.1
13.2
16.6
19.7

Advertisement

Table of Contents
loading

Table of Contents