1
3
2
3
1
Input power cabling
2
Motor cabling
3
Conduit
Continuous motor cable shield/conduit or enclosure for equipment
■
on the motor cable
To minimize the emission level when safety switches, contactors, connection boxes
or similar equipment are installed on the motor cable between the drive and the motor:
•
Install the equipment in a metal enclosure.
•
Use either a symmetrical shielded cable, or install the cabling in a metal conduit.
•
Make sure that there is a good and continuous galvanic connection in the
shield/conduit between drive and motor.
•
Connect the shield/conduit to the protective ground terminal of the drive and the
motor.
Separate control cable ducts
■
Put 24 V DC and 230 V AC (120 V AC) control cables in separate ducts, unless the 24 V DC
cable is insulated for 230 V AC (120 V AC) or insulated with an insulation sleeving for
230 V AC (120 V AC).
Guidelines for planning the electrical installation 73
1
1
3
3
2
3
230 V AC
24 V DC
(120 V AC)
1
2
2
230 V AC
24 V DC
(120 V AC)
3