Temp F
33.8
35.6
37.4
39.2
41.0
42.8
44.6
46.4
48.2
50.0
51.8
53.6
55.4
57.2
59.0
60.8
62.6
64.4
66.2
68.0
69.8
71.6
73.4
75.2
77.0
78.8
80.6
82.4
84.2
86.0
87.8
89.6
91.4
93.2
95.0
96.8
98.6
100.4
12
Table 3. Temp vs. OHM Values for MAS (Mixed Air Sensor)
Temp vs. OHM for MAS (Mixed Air Sensor)
Temp C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
R(K OHMS)
9.576
9.092
8.636
8.204
7.796
7.412
7.048
6.705
6.380
6.073
5.782
5.507
5.247
5.000
4.767
4.545
4.335
4.136
3.948
3.769
3.599
3.437
3.284
3.138
3.000
2.869
2.744
2.625
2.512
2.404
2.301
2.204
2.111
2.023
1.938
1.858
1.781
1.708
DC Volts
3.910
3.882
3.894
3.863
3.829
3.790
3.749
3.713
3.674
3.634
3.590
3.550
3.507
3.420
3.373
3.328
3.283
3.239
3.180
3.157
3.118
3.080
3.034
3.007
2.971
2.932
2.896
2.860
2.824
2.787
2.750
2.714
2.676
2.639
2.600
2.561
2.526
2.484