Technical Specifications - Carel EVD evolution User Manual

Electronic expansion valve driver
Hide thumbs Also See for EVD evolution:
Table of Contents

Advertisement

ENG
Power supply
(Lmax= 5 m)
Power input
Emergency power supply
Insulation between relay output and
other outputs
Motor connection
Digital input connection
Probes (Lmax=10 m;
S1
less than 30 m with
shielded cable)
S2
S3
S4
Relay output
Power to active probes (V
)
REF
RS485 serial connection
tLAN connection
pLAN connection
Assembly
Connectors
Dimensions
Operating conditions
Storage conditions
Index of protector
Environmental pollution
Resistance to heat and fi re
Immunity against voltage surges
Type of relay action
Class of insulation
Software class and structure
Conformity
"EVD evolution" +0300005EN - rel. 3.1 - 25.07.2011

11. TECHNICAL SPECIFICATIONS

24 Vac (+10/-15%) to be protected by external 2 A type T fuse.
24 Vdc (+10/-15%) 50/60 Hz to be protected by external 2 A type T fuse. Use a dedicated class 2 transformer (max 100 VA).
16.2 W with ALCO EX7/EX8 valves, 9.2 W with all other valves
35 VA with EVBAT00400; 35 VA with ALCO EX7/EX8 valves; 20 VA without EVBAT00400 and with all other valves
22 Vdc+/-5%. (If the optional EVBAT00200/300 module is installed), Lmax= 5 m
reinforced; 6 mm in air, 8 mm on surface; 3750 V insulation
4-wire shielded cable i.e. CAREL code E2VCABS*00, or 4-wire shielded cable AWG 22 Lmax= 10 m; or 4-wire shielded
cable AWG 14 Lmax= 50 m
Digital input to be activated from voltage-free contact or transistor to GND. Closing current 5 mA; Lmax= 30 m
ratiometric pressure probe (0 to 5 V):
• resolution 0.1 % FS;
• measurement error: 2% FS maximum; 1% typical
electronic pressure probe (4 to 20 mA):
• resolution 0.5 % FS;
• measurement error: 8% FS maximum; 7% typical
remote electronic pressure probe(4 to 20 mA), maximum number of drivers connected= 5:
• resolution 0.1 % FS;
• measurement error: 2 % FS maximum; 1 % typical
4 to 20 mA input (max 24 mA):
• resolution 0.5 % FS;
• measurement error: 8% FS maximum; 7% typical
low temperature NTC:
• 10kΩ at 25°C, -50T90 °C;
• measurement error: 1°C in the range -50T50°C; 3 °C in the range +50T90 °C
high temperature NTC:
• 50kΩ at 25°C, -40T150 °C;
• measurement error: 1.5 °C in the range -20T115°C, 4 °C in the range outside of -20T115 °C
NTC built-in:
• 10kΩ at 25 °C, -40T120 °C;
• measurement error: 1 °C in the range -40T50°C; 3 °C in the range +50T90 °C
0 to 10 V input (max 12 V):
• resolution 0.1 % FS;
• measurement error: 9% FS maximum; 8% typical
ratiometric pressure probe (0 to 5 V):
• resolution 0.1 % FS;
• measurement error: 2% FS maximum; 1% typical
electronic pressure probe (4 to 20 mA):
• resolution 0.5 % FS;
• measurement error: 8% FS maximum; 7% typical
electronic pressure probe (4 to 20 mA) remote. Maximum number of controllers connected=5
combined ratiometric pressure probe (0 to 5 V):
• resolution 0.1 % FS
• measurement error: 2 % FS maximum; 1 % typical
low temperature NTC:
• 10kΩ at 25°C, -50T105 °C;
• measurement error: 1 °C in the range -50T50 °C; 3°C in the range 50T90°C
high temperature NTC:
• 50kΩ at 25 °C, -40T150 °C;
• measurement error: 1.5 °C in the range -20T115 °C 4 °C in the range outside of -20T115 °C
NTC built-in:
• 10kΩ at 25 °C, -40T120 °C;
• measurement error 1 °C in the range -40T50 °C; 3 °C in the range +50T90 °C
normally open contact; 5 A, 250 Vac resistive load; 2 A, 250 Vac inductive load (PF=0 .4); Lmax=10 m
programmable output: +5 Vdc+/-2% or 12 Vdc+/-10%
Lmax=1000 m, shielded cable
Lmax=30 m, shielded cable
Lmax=500 m, shielded cable
DIN rail
plug-in, cable size 0.5 to 2.5 mm
2
(12 to 20 AWG)
LxHxW= 70x110x60
-10T60°C; <90% rH non-condensing
-20T70°C, humidity 90% rH non-condensing
IP20
2 (normal)
Category D
Category 1
1C microswitching
II
A
: EN 60730-1, EN 61010-1
Electrical safety
y: EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4; EN61000-3-2, EN55014-1,
Electromagnetic compatibilit
EN55014-2, EN61000-3-3.
Tab. 11.a
48