6.1 Power supply mode

EVD evolution can be powered at 24 Vac or 24 Vdc. In the event of direct
current power supply, after completing the commissioning procedure, to
start control set "Power supply mode" parameter=1.
Parameter/Description
ADVANCED
Power supply mode
0=24 Vac
1= 24 Vdc
Important: with direct current power supply, in the event of power
failures emergency closing of the valve is not performed, even if the
EVBAT00400 battery module is connected.

6.2 Network connection

To connect an RS485/Modbus® controller to the network, as well as the
network address parameter (see paragraph 4.2), the communication
speed also needs to be set, in bit/s, using the "Network settings" parameter.
Parameter/Description
ADVANCED
NETWORK SETTINGS
0=4800
1=9600
2=19200
Note: the following Modbus® serial communication parameters
cannot be set:
byte size: 8 bits;
stop bits: 2;
parity: none;
transmission mode: RTU.

6.3 Inputs and outputs

Analogue inputs
The parameters in question concern the choice of the type of pressure
probe S1 and S3 and the choice of the temperature probe S2 and S4,
as well as the possibility to calibrate the pressure and temperature
signals. As regards the choice of pressure probe S1, see the chapter on
"Commissioning".
Inputs S2, S4
The options are standard NTC probes, high temperature NTC, combined
temperature and pressure probes and 0 to 10 Vdc input. For S4 the
0 to 10 Vdc input is not available. When choosing the type of probe,
the minimum and maximum alarm values are automatically set. See
the chapter on "Alarms". The auxiliary probe S4 is associated with the
Modulating thermostat function or can be used as a backup probe for
the main probe S2.
Type
CAREL NTC (10KΩ at 25°C)
CAREL NTC-HT HT (50KΩ at 25°C) NTC0**HT00
NTC built-in
Important: in case of NTC built-in probe, select also the parameter
relevant to the corresponding ratiometric pressure probe.

6. FUNCTIONS

Def.
Min.
Max.
UOM
0
0
1
-
Tab. 6.a
Def.
Min.
Max.
UoM
2
0
2
bit/s
Tab. 6.b
CAREL code
Range
NTC0**HP00
-50T105°C
NTC0**WF00
NTC0**HF00
0T120°C
(150 °C per 3000 h)
SPKP**T0
-40T120°C
Tab. 6.c
Parameter/description
CONFIGURATION
Probe S2:
CAREL NTC; CAREL NTC-HT high T; NTC built-in SPKP**T0;
0-10 V external signal
Probe S4:
CAREL NTC; CAREL NTC-HT high T; NTC built-in SPKP**T0
Input S3
The auxiliary probe S3 is associated with the high condensing
temperature protection or can be used as a backup probe for the main
probe S1. If the probe being used is not included in the list, select any
0 to 5 V ratiometric or electronic 4 to 20 mA probe and then manually
modify the minimum and maximum measurement in the manufacturer
parameters corresponding to the probes.
Important: probes S3 and S4 appear as NOT USED if the "auxiliary
control" parameter is set as "disabled".
If "auxiliary control" has any other setting, the manufacturer setting for the
probe used will be shown, which can be selected according to the type.
Auxiliary control
High condensing temperature protection
Modulating thermostat
Backup probes
Parameter/description
Confi guration
Probe S3:
Ratiometric (OUT=0 to 5 V) Electronic (OUT=4 to 20 mA)
1= -1 to 4.2 barg
2= 0.4 to 9.3 barg
3= -1 to 9.3 barg
4= 0 to 17.3 barg
5= 0.85 to 34.2 barg
6= 0 to 34.5 barg
7= 0 to 45 barg
21= -1 to 12.8 barg
22= 0 to 20.7 barg
23= 1.86 to 43.0 barg
Calibrating pressure probes S1, S3 and temperature
probes S2 and S4 (o set and gain parameters)
In case it is necessary to make a calibration:
of the pressure probe, S1 and/or S3 it is possible to use the off eset
parameter, which represents a constant that is added to the signal
across the entire range of measurement, and can be expressed in
barg/psig. If the 4 to 20 mA signal coming from an external controller
on input S1 needs to be calibrated, both the off set and the gain
parameters can be used, the latter which modifi es the gradient of the
line in the fi eld from 4 to 20 mA.
of the temperature probe, S2 and/or S4 it is possible to use the off set
parameter, which represents a constant that is added to the signal
across the entire range of measurement, and can be expressed in °C/°F.
If the 0 to 10 Vdc signal coming from an external controller on input
S2 needs to be calibrated, both the off set and the gain parameters can
be used, the latter which modifi es the gradient of the line in the fi eld
from 0 to 10 Vdc.
"EVD evolution" +0300005EN - rel. 3.1 - 25.07.2011
27
Def.
CAREL NTC
CAREL NTC
Variable displayed
S3
S4
S3,S4
Def.
Ratiom.: -1 to
9.3 barg
8= -0.5 to 7 barg
9= 0 to 10 barg
10= 0 to 18,2 barg
11= 0 to 25 barg
12= 0 to 30 barg
13= 0 to 44.8 barg
14= remote, -0.5 to 7 barg
15= remote, 0 to 10 barg
16= remote, 0 to 18,2 barg
17= remote, 0 to 25 barg
18= remote, 0 to 30 barg
19= remote, 0 to 44.8 barg
20= 4-20 mA external signal
( cannot be selected)
ENG
Tab. 6.d
Tab. 6.e
Tab. 6.f