Shared Pressure Probe; Connecting The Usb-Tlan Converter; Connecting The Usb/Rs485 Converter; Upload, Download And Reset Parameters (Display) - Carel EVD evolution User Manual

Electronic expansion valve driver
Hide thumbs Also See for EVD evolution:
Table of Contents

Advertisement

Note: operation in parallel and complementary mode can only be
used for CAREL valves, within the limits shown in the table below, where
OK means that the valve can be used with all refrigerants at the rated
operating pressure.
Model of CAREL valve
E2V*
E3V*
E4V*
Two EXV connected
OK
OK
E4V85 with all refrigerants except
together
for R410A
E4V95 only with R134a

2.6 Shared pressure probe

Only 4 to 20 mA pressure probes (not ratiometric) can be shared. The
probe can be shared by a maximum of 5 drivers. For multiplexed systems
where controllers EVD evolution1 to EVD evolution5 share the same
pressure probe, choose the normal option for EVD evolution1 and the
"remote" option for the other drivers, up to the fi fth. EVD evolution6 must
use another pressure probe P2.
EXAMPLE
EVD Evolution1
to
Probe S1
-0.5 to 7 barg (P1)
to
EVD Evolution 5
EVD Evolution 1
GND
Tx/Rx
P1
Key:
P1
Shared pressure probe
P2
Pressure probe

2.7 Connecting the USB-tLAN converter

Procedure:
remove the LED board cover by pressing on the fastening points;
plug the adapter into the service serial port;
connect the adapter to the converter and then this in turn to the
computer.
power up the driver.
Fig. 2.g
4
EVDCNV00E0
3
Fig. 2.h
Key:
1
service serial port
2
adapter
3
USB/tLAN converter
4
personal computer
E5V*
E6V*
E7V*
NO
NO
NO
EVD Evolution5
EVD Evolution6
remote, -0.5 to 7 barg
-0.5 to 7 barg (P2)
EVD Evolution 6
GND
Tx/Rx
GND
Tx/Rx
P2
press
press
1
3
2
4
1
NET
OPEN
CLOSE
2
GND
Tx/Rx
Note: when using the service serial port connection, the VPM
program can be used to confi gure the driver and update the driver
and display fi rmware, downloadable from http://ksa.carel.com.
See the appendix.

2.8 Connecting the USB/RS485 converter

Only on EVD evolution RS485/Modbus® models can the confi guration
computer be connected using the USB/RS485 converter and the serial
port, according to the following diagram.
1
3
OPEN
CLOSE
EVD evolution
Analog - Digital Input
Key:
1
2
Note:
• the serial port can be used for confi guration with the VPM program and
for updating the driver fi rmware, downloadable from http://ksa.carel.com;
• to save time, up to 8 EVD evolution drivers can be connected to the
computer, updating the fi rmware at the same time (each driver must
have a diff erent network address).
2.9 Upload, Download and Reset parameters
(display)
Procedure:
10.
press the Help and Enter buttons together for 5 seconds;
11.
a multiple choice menu will be displayed, use UP/DOWN to select the
required procedure;
12.
confi rm by pressing ENTER;
13.
the display will prompt for confi rmation, press ENTER;
14.
at the end a message will be shown to notify the operation if the
operation was successful.
UPLOAD: the display saves all the values of the parameters on the
source driver;
DOWNLOAD: the display copies all the values of the parameters to the
target driver;
RESET: all the parameters on the driver are restored to the default
values. See the table of parameters in chapter 8.
Important:
the procedure must be carried out with driver powered;
DO NOT remove the display from the driver during the UPLOAD,
DOWNLOAD, RESET procedure;
the parameters cannot be downloaded if the source driver and the
target driver have incompatible fi rmware.
"EVD evolution" +0300005EN - rel. 3.1 - 25.07.2011
11
2
4
NET
1
Network
GND
Tx/Rx
shield
2
Fig. 2.i
personal computer for confi guration
USB/RS485 converter
Fig. 2.j
ENG

Hide quick links:

Advertisement

Table of Contents
loading