5.3 InSignal adaptation

5.3.1 SIGNAL (Type of input signal)

Command
SIGNAL:I
This command can be used to change the type of input signal (voltages or current) and to define the direction
of the signal. This command is available for all analogue inputs (W and X).
OFF= Deactivation of the input

5.3.2 N_RANGE:X (Sensor nominal pressure)

Command
N_RANGE:X X
This command defines the nominal working range of the feedback sensor. Wrong parameterization causes
wrong system settings. The control parameters cannot be calculated correctly in case of wrong values.
The N_RANGE:X value is set per cent in relation to the working range. Because this is a universal controller,
the working range of the system is defined to 100% as reference value. The N_RANGE should not be set
lower than 100% if possible-

5.3.3 OFFSET:X (Sensor offset)

Command
OFFSET:X
Adjustment of the zero point of the sensor. Reference value is always the working range.
Page 21 of 34
Parameters
X
i= W|X
x= OFF|U0-10|I4-20
Parameter
x= 1... 10000
Parameter
X
x= -60000... 60000
PQP-171-P
Unit
Group
-
EASY
Unit
Group
%
EASY
Unit
Group
0.01 %
EASY
05.06.2020