Parameters; Parameter Overview - WEST PQP-171-P Technical Documentation Manual

Universal pump control module
Table of Contents

Advertisement

5 Parameters

5.1 Parameter overview

Group
Command
Basic parameters
LG
MODE
FIXCURR
CTRLMODE
CCMODE
SENS
EOUT
Input signal adaptation
Sensor scaling
SIGNAL:X
N_RANGE:X
OFFSET:X
Command signal scaling
SIGNAL:W
Ramp function
RA:UP
RA:DOWN
Characteristic linearization
CC
Control parameters
PID controller
C:P
C:I
C:D
C:D_T1
C:OFFSET
Integrator control
C:I_LIM
Extended control parameter
C_EXT:P
C_EXT:T1
C_EXT_FF
Output signal adaptation
MIN:A
MIN:B
MAX:A
MAX:B
TRIGGER
SIGNAL:U
Page 17 of 34
Default
Unit
EN
-
Changing language help texts
STD
-
Parameter view
Fix output value for corresponding digital input
OL
-
Closed loop (CL) or open loop (OL) control.
OFF
-
Activation / deactivation of the CC function.
ON
-
Malfunction monitor
0
0.01 %
Output signal if not ready
U0-10
V
Type of input
100
%
Sensor working range in relation to system working range
0
0.01 %
Sensor offset
U0-10
mbar
Type of input
100
ms
Command signal ramp times
100
ms
X
Y
0,01 %
X Y parameter for up to 10 points.
100
0.01
P gain
4000
0.1 ms
I gain
0
0.1 ms
D gain
500
0.1 ms
D gain filter
0
0.01 %
Direct control
2500
0.01 %
Integrator limitation
0
0.01
P gain
200
0.1 ms
P gain filter
0
0.01 %
Feed forward
0
0.01 %
Deadband compensation
0
0.01 %
10000
0.01 %
Output scaling
10000
0.01 %
200
0.01 %
Deadband compensation trigger point
1S+
-
Type and polarity of the output
PQP-171-P
Description
05.06.2020

Advertisement

Table of Contents
loading

Table of Contents