Calculating the Supply Water Temperature _________________ 9 Calculating the Floor Surface Temperature ________________ 10 Calculating the Pressure Drop ___________________________ 11 Selecting a Circulator Pump ____________________________ 12 Climate Trak / Heat Transfer Plate System Installation _______ 13 Pre-Installation Tips ____________________________________ 13 4.1.1 Avoiding Obstructions ___________________________ 13...
Page 4
Appendix F: Making a Material List_________________________ 37 13.1 Climate Trak Material Worksheets ________________________ 37 Limited Warranty _________________________________________ 38 14.1 Limited Warranty for Viega Heating and Cooling Solutions ___ 38 List of Tables Table 1 Multipliers for Climate Traks _____________________________ 7...
This document is subject to updates. For the most current Viega technical literature please visit www.viega.us. Viega products are designed to be installed by licensed and trained plumbing and mechanical professionals who are familiar with Viega products and their installation. Installation by non-professionals may void Viega LLC’s warranty.
These types of applications are not the most efficient kind of radiant heating compared to systems such as Viega Climate Panel and Viega Snap Panel, but deliver the comfort of having warm floors and full radiant heating throughout the house. Both methods utilize Viega Barrier PEX tubing and attach directly to the underside of the subfloor.
3.2 Heat Loss Calculations for Floor Heating Systems Please reference ACCA Manual J, the ASHRAE Handbook, or CSA F280- 12 to determine heat loads. Viega offers software that will perform a full, multi-temperature, room by room, detailed design while calculating a materials list and price quote for your system.
2. Follow to the right until you reach the selected total R-value curve. 3. Then move down to the horizontal axis and read the supply water temperature. (For additional Climate Trak/Heat Transfer Plate BTU output charts, refer to Appendix E). 0.25 Supply Water Temperature (°F)
The floor surface temperature will be 80°F with 25 BTU/h/ft output and 68°F room temperature. This chart shows the relation between room temperature and floor surface temperature for floor heating systems. Floor Surface Temperature Chart 10 of 40 IM-HC 530590 0621 Climate Trak (EN)
4. Multiply pressure drop per foot by length of longest circuit. Example: GPM through ½” Viega Barrier PEX tubing: 0.7 GPM Pressure drop per foot: ~ 0.022 ft. of head / ft. Total pressure drop: 0.022 x 350 total ft. = 7.7 ft. of head...
3. Follow to the intersection of both variables. 4. Select the pump with a curve higher than this point. Example: Total GPM through ½" Viega Barrier PEX: 5 GPM Longest circuit pressure drop: 10 ft. of head Pump selected: Low Head Pump...
Climate Trak / Heat Transfer Plate System Installation 4 Climate Trak / Heat Transfer Plate System Installation 4.1 Pre-Installation Tips Place the Traks for the most even heat distribution. Dimensions in drawing are based on standard 2" by 8", 2" by 10", or 2"...
Climate Trak / Heat Transfer Plate System Installation 4.2 Clearing the Bays If support crosses can be easily removed, take them out to clear bays for easier installation of the plates and Traks. If crosses are unable to be removed, DO NOT drop tubing below them and resume on the other side;...
Climate Trak / Heat Transfer Plate System Installation 4.4 Attaching the Traks/Plates Start attaching the Traks via staples or zip screws (staples: " to ½" crown by ¾" to 1", depending upon subfloor thickness; putting in 18 to 20 staples for an 8 ft. piece and 10 to 12 staples for a 4 ft. piece; zip screws ¾"...
Climate Trak / Heat Transfer Plate System Installation 4.5 Installing the Tubing Begin to make non-stressful (teardrop) type loops for each of the bays, keeping loops small and manageable. Continue making the “teardrop” loops, being sure not to install any of the tubing into the Traks yet.
Climate Trak / Heat Transfer Plate System Installation Continue transferring the tubing through the loops, finishing one bay at a time. 4.6 Post-Installation Tips - Insulation Insulation should always be used in a staple-up radiant installation. Ideally there should a 1" to 2" air gap in between the insulation and the Traks/ Plates.
In many applications either an Injection or Mixing Station can be used; Reducers however, because a staple-up system generally uses 10-20° higher water temperature, Viega recommends only using a Mixing Station with this type of application. Mixing Station includes: 2 - Ball valves 1 - Pump (low, medium, high) 1 - Diverting valve with integrated high temp.
All schematics are conceptual. The designer must determine whether this application will work in the system and must ensure compliance with national and local code requirements. Boiler trim (expansion tank, fill valve, relays, etc.) supplied by others. IM-HC 530590 0621 Climate Trak (EN) 19 of 40...
Table 7: Single Temperature Radiant System Materials A.H.C Primary Pump Supply Sensor System Pump 3 Position Actuator Return Manifold 3 Position Actuator Air Eliminator Back Flow Preventor Cold Water Supply Pressure Reducing Valve Expansion Tank Supply Manifold 20 of 40 IM-HC 530590 0621 Climate Trak (EN)
Code, applicable local code and pertinent industry standards. 5.3.2.1 Wiring Schematic: One Zone Application Digital Thermostat NTC A/B C C R W Floor sensor Digital Thermostats can control up to 4 powerheads. 22 of 40 IM-HC 530590 0621 Climate Trak (EN)
MAIN EXTRA N/O COM N/C SWITCH SWITCH BOILER SYSTEM CIRCULATOR DHW CIRCULATOR NEUTRAL 120 VAC 4 Zone Control (18060) can operate 8 powerheads. 6 Zone Control (18062) can operate 16 powerheads. IM-HC 530590 0621 Climate Trak (EN) 23 of 40...
Mixing Station on the copper tee. Install tees as close as possible to keep pressure difference at a minimum. 3. Connect the supply and return lines by soldering on a Viega PEX Press adapter, then pressing on Viega Barrier PEX.
System Start-Up 4. Use the SVC Compression or PEX Press Adapters to connect the Viega Barrier PEX lines to the manifold. 5. Remove the grey cap from the diverting valve on the Mixing Station and screw the actuator on hand tight.†...
Before the finish floor is installed, the radiant system must be pressure tested. Air or water may be used as the medium. The following procedure is recommended by Viega. Check the local building codes for compliance or additional test requirements.
Tighten (A) hex lock nut with wrench. Do not overtighten. To secure high limit adjustment: hold slotted adjustment screw with brass key while tightening nut. IM-HC 530590 0621 Climate Trak (EN) 27 of 40...
2. To decrease flow, turn the balancing valve clockwise in small increments. Remove red caps and turn balancing valves with included allen key. Valves are hidden to prevent tampering. Balancing Valves 28 of 40 IM-HC 530590 0621 Climate Trak (EN)
Vinyl flooring is another common choice for kitchens and baths and has a low R-value. Using carpet over radiant heating requires careful planning. Viega’s recommendation for a covering over a radiant system is to not exceed a total of a 2.5 R-value (the carpet pad plus the carpet itself).
Engineered wood flooring usually has less expansion and contraction and can be a good choice to minimize gaps between planks. Note: Follow the flooring manufacturer’s installation manual or NOFMA’s (National Oak Flooring Manufacturers Association) manual. 30 of 40 IM-HC 530590 0621 Climate Trak (EN)
PureFlow press connection. 9 Appendix B: SVC Compression Coupling ⅜" to ⅝" SVC Compression Couplings Product Instructions www.viega.us for information on how to make an SVC Compression Couplings connection. IM-HC 530590 0621 Climate Trak (EN) 31 of 40...
12 Appendix E: Supply Water Temperature/BTU Output Charts 0.25 Supply Water Temperature (°F) Based on 68°F room temperature with R19 insulation between joists 0.25 Supply Water Temperature (°F) Based on 68°F room temperature with R19 insulation between joists 34 of 40 IM-HC 530590 0621 Climate Trak (EN)
Page 35
Appendix E: Supply Water Temperature/BTU Output Charts 0.25 Supply Water Temperature (°F) Based on 68°F room temperature with R19 insulation between joists 0.25 Supply Water Temperature (°F) Based on 68°F room temperature with R19 insulation between joists IM-HC 530590 0621 Climate Trak (EN) 35 of 40...
Page 36
Appendix E: Supply Water Temperature/BTU Output Charts 0.25 Supply Water Temperature (°F) Based on 68°F room temperature with R19 insulation between joists 0.25 Supply Water Temperature (°F) Based on 68°F room temperature with R19 insulation between joists 36 of 40 IM-HC 530590 0621 Climate Trak (EN)
Powerheads for Brass Manifold PEX Press Adapters Manifold Compression PEX Adapters These charts are intended for conceptual purposes only; there may be variations in each job. Table 12: Climat Trak Material Worksheets IM-HC 530590 0621 Climate Trak (EN) 37 of 40...
(30) years from date of initial installation; warrants that any accessible metal compression or metal/polyalloy crimp fittings, manifolds and panels sold by Viega and used in the systems will be free from failure caused by manufacturing defect for a period of five (5) years,...
Page 39
Viega will investigate the reasons for the failure, which includes the right to inspect the product at Viega and reasonable access to the site of the damage in order to determine whether the warranty applies. Viega will notify you in writing of the results of its review.
Page 40
, and Viega: Connected in quality are trademark of Viega ® ® ® Holding GmbH & Co. KG. XL-C is a registered trademark of Viega LLC. Eco Brass is a registered ® ® www.viega.us trademark of Mitsubishi Shindoh Co., LTD. RIDGID ®...
Need help?
Do you have a question about the Climate Trak and is the answer not in the manual?
Questions and answers