Page 1
GRUNDFOS INSTRUCTIONS Fire CONTROLLER SS EN12845 SS 883001 Installation and operating instructions INSTA 900...
Page 2
We, Grundfos, declare under our sole responsibility that the product Fire We, Grundfos, declare under our sole responsibility that the product Fire RS, to which this declaration relates, is in conformity with these RS, to which this declaration relates, is in conformity with these Council...
The risk is 12.3 Test run carried solely by the operator. Shut down In particular, the use of the Fire RS extinguishing water booster Maintenance set to supply water or boost pressure in daily operation is 14.1 Pumps regarded as not in accordance with the intended use.
4.3.1 General description Control panel (A1) Control panel (A1) The Fire RS extinguishing water booster set is operated via a The Fire RS extinguishing water booster set is operated via a The control panel contains the buttons required for control and controller especially designed for this purpose.
4.4 Functions 4.4 Functions Pos. Designation Pos. Designation 4.4.1 Operating functions 4.4.1 Operating functions Main fuse Main fuse Automatic operation of the main pump Automatic operation of the main pump FA2 Fuse for 24 V control circuit Fuse for 24 V control circuit Automatic operation is the normal operating Automatic operation is the normal operating FA3 Fuse for 230 V control circuit...
Page 7
Manual operation of the jockey pump set nameplate, the nameplate of the pump, the nameplate of the 5. Identification Manual operation of the jockey pump electric motor, and the nameplate of the controller. Nameplate of During start-up and for test purposes, the jockey pump can be During start-up and for test purposes, the jockey pump can be All important data of the extinguishing water booster set and its the controller...
6.3 Controller Type key for controller 6.3 Controller Type key for controller Control cabinet: Sheet steel, grey. Control cabinet: Sheet steel, grey. Example AVV. QST + J EN / 1x 5,8 kW -SD 1x 0,65kW -DOL Example AVV. QST + J EN / 1x 5,8 kW -SD 1x 0,65kW -DOL Enclosure class: IP54. Enclosure class: IP54.
8. Control panel 8. Control panel The control panel is only used for operating The control panel is only used for operating the the main pump. To operating elements and main pump. To operating elements and signal signal lamps for the jockey pump are described Note lamps for the jockey pump are described in Note...
8.2 Status indications 8.2 Status indications The operating status of the main pump and the controller is indicat- The operating status of the main pump and the controller is ed by means of three indicator lights under “Status” in the control indicated by means of three indicator lights under "Status"...
8.3 Fault indications 8.3 Fault indications Faults of the main pump are indicated by means of the two indica- Faults of the main pump are indicated by means of the two tor lights under “Alarms” in the control panel. Faults of the jockey indicator lights under "Alarms"...
Furthermore, any wires or water and gas pipes. Furthermore, 10.1.4 Piping The extinguishing water booster set Fire RS EN CR with its missioning are considerable. ensure safe installation. ensure safe installation.
10.2 Electrical connection 11. Commissioning 10.2 Electrical connection 11. Commissioning Warning Warning Warning Warning Start-up must be carried out by authorised During electrical installation, make sure that the Start-up must be carried out by authorised During electrical installation, make sure that the personnel.
Page 15
Step Illustration Step Illustration Step Illustration Step Illustration 5. Turn the selector 10. Stop the main pump 5. Turn the selector 10. Stop the main pump switch for the jockey manually by pressing switch for the jockey manually by pressing pump to “MAN”...
12. Operation Stopping the jockey pump 12. Operation Stopping the jockey pump Warning Warning The control cabinet must remain closed during The control cabinet must remain closed during operation. Risk of electric shock! operation. Risk of electric shock! Ensure sufficient ventilation of the controller! Caution Caution Ensure sufficient ventilation of the controller!
12.2 Manual operation Stopping procedure 12.2 Manual operation Stopping procedure Both pumps can also be started and stopped manually for a Both pumps can also be started and stopped manually for a Step Illustration functional test, at start-up or after service work. Step Illustration functional test, at start-up or after service work.
Page 18
12.2.2 Main pump Stopping procedure 12.2.2 Main pump Stopping procedure Starting procedure Starting procedure Step Illustration Step Illustration Step Illustration Step Illustration 1. Stop the main pump manual- 1. Stop the main pump ly by pressing the [Stop] button. manually by pressing 1.
12.3 Test run 12.3 Test run Step Illustration Do not leave the pump room during the test run. Do not leave the pump room during the test run. 5. Start the main pump 5. Start the main pump by Observe all operating and fault indications as the Observe all operating and fault indications as the by pressing the [P2] pressing the [P2]...
To test the indicator lights of the control panel, press To test the indicator lights of the control panel, press See fig. 10. If an indicator light fails, please contact Grundfos. See fig. 10. If an indicator light fails, please contact Grundfos.
15. Fault finding 15. Fault finding Warning Warning Only trained personnel are allowed to open the cabinet door. Only trained personnel are allowed to open the cabinet door. Warning Warning Before removing the terminal box cover on the motor, opening the control cabinet or before any service work on the Before removing the terminal box cover on the motor, opening the control cabinet or before any service work on the sprinkler pump system, the mains supply must be completely disconnected and it must be ensured that it cannot be ac- sprinkler pump system, the mains supply must be completely disconnected and it must be ensured that it cannot be...
Page 22
Fault Possible cause Remedy Fault Possible cause Remedy 7. Jockey pump does not a) Selector switch for jockey pump not in position 7. Jockey pump does not a) Selector switch for jockey pump not in position Turn the selector switch to position “MAN” Turn the selector switch to position "MAN"...
The usage of non-authorised spare parts and accessories renders The usage of non-authorised spare parts and accessories any liability on behalf of Grundfos for resulting damages null and renders any liability on behalf of Grundfos for resulting damages void.