Wiring Connections - Trane BAYECON300 Series Installation Instructions Manual

0-100% down flow dry bulb economizer foundation packaged cooling and gas/electric
Table of Contents

Advertisement

Minimum Position Setting
To adjust the minimum position setting and check out the
economizer, the power must be connected.
Close the unit disconnect and place the zone sensor fan
selector in the fan "ON" position and the heat/cool selector
in the "OFF" position. This will place the damper in the
minimum ventilation position.
To adjust the minimum position setting for the required
ventilation air, turn the potentiometer (on the ECA)
clockwise to "open" (to increase the amount of ventilation)
or counterclockwise to "close" (to decrease the amount of
ventilation). The damper will open to this setting each time
the blower circuit is energized.
When adjusting minimum position, the damper may move
to the new setting in several small steps. Once the damper
has remained in position for 10 - 15 seconds without
movement, it can be assumed it is at the new position.
Replace the filter access panel.
The damper will close when the blower circuit is de-
energized.
Dry Bulb Settings
Standard economizer dry bulb changeover is field
selectable to 5 outdoor temperatures. See
potentiometer settings.The selection is made on the ECA.
Reference Enthalpy Settings
Economizer enthalpy changeover is field selectable to 5
points. See
Table 1
for potentiometer settings. The
selection is made on the ECA.
Table 1.
Potentiometer settings
Potentiometer
Setting
Dry Bulb
A
73ºF (22.8ºC)
B
70ºF (21.1ºC)
(a)
C
67ºF (19.4ºC)
D
63ºF (17.2ºC)
E
55ºF (12.8ºC)
(a) Factory Setting
ACC-SVN155D-EN
Table 2.
Dry Bulb (standard)
Reference Enthalpy
Comparative Enthalpy
(a) Economizing is enabled when these conditions are met.
(b) Conditions level will be self configured when optional sensors are con-

Wiring Connections

Locate unit wiring harness plug PPM2A. The plug is
located in the upper left section of the return air section.
Remove the cap covering the plug, and connect to the
economizer wiring harness.
Figure 24. Electromechanical wiring
Table 1
for
Enthalpy
27 Btu/lb (63 kJ/kg)
25 Btu/lb (58 kJ/kg)
23 Btu/lb (53 kJ/kg)
22 Btu/lb (51 kJ/kg)
19 Btu/lb (44 KJ/Kg)
Economizer control options
Enable
Control Option
Conditions
See
See
(ReliaTel Only)
Outdoor Air Enthalpy
3.0 BTU/lb. less than
(ReliaTel Only)
Return Air Enthalpy
nected.
Installation
Optional Sensors
(a)
(b)
Required
Outdoor Air Temp
Table 1
(OAT)
Outdoor Humidity
Table 1
(BAYENTH300*)
Outdoor Humidity
Return Humidity
Return Temperature
(BAYENTH301*)