Wiring Precautions; Outdoor Wiring Connections - Trane RunTru 17 Series Installer's Manual

System (r-410a) mini-split, inverter system
Table of Contents

Advertisement

Wiring Precautions

1. Before obtaining access to terminals, all supply circuits must be disconnected.
2. Improperly installed and grounded field wiring poses fire and electrocution hazards. For
high voltage connections, flexible electrical conduit is recommended whenever vibration
transmission may create a noise problem within the structure. To avoid these hazards, you
MUST follow requirements for field wiring installation and grounding as described in the
National Electrical Codes (NEC) and your local/state electrical codes. All field wiring MUST
be performed by qualified personnel. Failure to follow these requirements could result in
death or serious injury.
1. EACH unit should be installed with its own dedicated power supply source. The power source
needs to be sized correctly for the unit capacity.
2. The rated voltage of the unit is as shown in this manual.
3. Before turning on, verify that the voltage is within the 187~252 V range (for 208/230 V, single
phase units).
4. Always use a grounded terminal and install a separate receptacle to supply power to the
air conditioner. For high voltage connections, flexible electrical conduit is recommended
whenever vibration transmission may create a noise problem within the structure.
5. Use a dedicated breaker and receptacle matched to the capacity of the air conditioner.

Outdoor Wiring Connections

1. Remove the wire clip and connect the power connection wire and signal control wire terminals
according to the color coding.
2. Attach the wires to the terminals and make sure they are securely fastened. Refer to wiring
diagrams in this manual. An example is provided in the figure below:
green
(yellow-
green)
NOTE: The wiring diagrams in this guide are included as a reference. The manufacturer
has a policy of continuous product and product data improvement and reserves the
right to change design and specifications without notice. Always check the unit
nameplate and wiring diagram for the actual unit requirements.
88-M4MHW17-1A-EN
Electrical Notes:
09、 12K
N(1) 2
3
L2
L1
white
red
black
white
(blue)
black (brown)
(brown)
(blue)
L2
L1
Indoor unit connection
POWER
WARNING
green
(yellow-
green)
Installer's Guide
18、 24K:
N(1)
2
3
L1
L2
green
white
red
black
white
(yellow-
(blue)
black (brown)
(brown)
(blue)
green)
L1
L2
Indoor unit connection
POWER
green
(yellow-
green)
25