Blower Performance - Daikin GPGM5 Installation Instructions Manual

15.2 seer2 “m” series 2-4 ton single package gas-electric heating & cooling units
Hide thumbs Also See for GPGM5:
Table of Contents

Advertisement

BLOWER PERFORMANCE DATA
T1 LOW STAGE HEATING
E.S.P.
CFM
0.1
700
0.2
665
0.3
614
0.4
561
0.5
505
0.6
438
0.7
374
0.8
318
T1 LOW STAGE HEATING
E.S.P.
CFM
0.1
1035
0.2
990
0.3
950
0.4
910
0.5
865
0.6
820
0.7
765
0.8
725
T1 LOW STAGE HEATING
E.S.P.
CFM
0.1
950
0.2
895
0.3
840
0.4
775
0.5
710
0.6
650
0.7
590
0.8
540
T1 LOW STAGE HEATING
E.S.P.
CFM
0.1
1100
0.2
1040
0.3
985
0.4
920
0.5
875
0.6
815
0.7
765
0.8
710
T1 LOW STAGE HEATING
E.S.P.
CFM
0.1
1085
0.2
1035
0.3
985
0.4
925
0.5
870
0.6
815
0.7
760
0.8
710
X = Outside of Temperature Rise Range Not Recommended.
GPGM52406041 - Rise Range: 25° - 55°
T2 HIGH STAGE HEATING
SPEED
WATTS
RISE
CFM
76
48
1080
84
51
1032
91
55
988
98
60
948
105
67
902
114
77
859
119
90
813
125
106
770
GPGM530080M41 - Rise Range: 35° - 65°
T2 HIGH STAGE HEATING
SPEED
WATTS
RISE
CFM
156
43
1300
165
45
1265
173
47
1220
184
49
1190
190
52
1145
200
55
1105
204
59
1070
211
62
1015
GPGM53608041 - Rise Range: 35° - 65°
T2 HIGH STAGE HEATING
SPEED
WATTS
RISE
CFM
115
47
1245
124
50
1195
134
54
1150
146
58
1095
152
63
1045
160
X
990
163
X
935
171
X
870
GPGM54210041 - Rise Range: 35° - 65°
T2 HIGH STAGE HEATING
SPEED
WATTS
RISE
CFM
172
51
1420
181
54
1360
185
57
1310
193
61
1275
203
64
1210
207
X
1165
215
X
1115
216
X
1075
GPGM54810041 - Rise Range: 35° - 65°
T2 HIGH STAGE HEATING
SPEED
WATTS
RISE
CFM
171
52
1410
178
54
1365
184
57
1315
193
61
1270
198
65
1220
208
X
1175
213
X
1115
219
X
1080
T3 LOW STAGE
SPEED
COOLING SPEED
WATTS
RISE
CFM
197
42
744
204
44
696
212
46
646
220
47
591
225
50
524
231
52
466
238
55
405
245
58
356
T3 LOW STAGE
SPEED
COOLING SPEED
WATTS
RISE
CFM
287
46
848
293
47
797
310
49
740
306
50
680
319
52
615
320
54
551
330
56
462
338
59
384
T3 LOW STAGE
SPEED
COOLING SPEED
WATTS
RISE
CFM
230
48
960
238
50
897
247
52
828
256
55
766
263
57
695
277
61
634
285
64
571
288
X
509
T3 LOW STAGE
SPEED
COOLING SPEED
WATTS
RISE
CFM
325
53
1210
331
55
1140
342
57
1085
353
59
1023
360
62
963
368
64
901
369
X
846
385
X
786
T3 LOW STAGE
SPEED
COOLING SPEED
WATTS
RISE
CFM
326
53
1326
329
55
1273
337
57
1222
353
59
1172
360
61
1123
372
64
1073
375
X
1027
381
X
978
26
T4 HIGH STAGE
COOLING SPEED
WATTS
CFM
WATTS
72
1021
149
79
976
157
86
932
164
93
885
171
99
844
178
106
795
185
111
744
192
116
983
199
T4 HIGH STAGE
COOLING SPEED
WATTS
CFM
WATTS
89
1171
201
96
1127
208
104
1087
217
112
1043
224
120
990
231
126
941
239
132
885
245
138
826
251
T4 HIGH STAGE
COOLING SPEED
WATTS
CFM
WATTS
134
1450
396
142
1400
405
148
1349
413
156
1302
420
163
1253
428
168
1203
436
173
1152
442
178
1102
449
T4 HIGH STAGE
COOLING SPEED
WATTS
CFM
WATTS
220
1571
430
226
1520
439
235
1472
448
243
1403
454
250
1356
463
259
1302
470
266
1247
476
271
1188
480
T4 HIGH STAGE
COOLING SPEED
WATTS
CFM
WATTS
287
1601
733
294
1544
744
303
1485
751
311
1435
760
319
1383
766
328
1333
779
337
1279
787
344
1219
792
T5 COOLING SPEED
WATTS
CFM
197
1090
201
1055
207
1020
212
995
230
955
240
915
255
880
246
835
T5 COOLING SPEED
WATTS
CFM
1295
289
1260
294
1220
304
1180
313
1140
319
1105
326
1055
334
1015
337
T5 COOLING SPEED
WATTS
CFM
1440
354
1390
365
1355
369
1300
383
1260
396
1210
402
1160
397
1110
415
T5 COOLING SPEED
WATTS
CFM
1620
484
1575
489
1530
497
1490
500
1450
507
1405
518
1345
516
1300
528
T5 COOLING SPEED
WATTS
CFM
1790
641
1745
650
1710
659
1670
663
1625
674
1585
672
1540
675
1495
683

Advertisement

Table of Contents
loading

Table of Contents