DCG180 STANDARD BELT DRIVE (includes 2 speed models at high speed)
ESP, In H
O
2
0
CFM
BHP
0.2
---
---
0.4
---
---
0.6
---
---
0.8
6717
3.42
1.0
5975
2.99
1.2
5147
2.55
DCG240 STANDARD BELT DRIVE (includes 2 speed models at high speed)
ESP, In H
O
0
2
CFM
BHP
0.2
---
---
0.4
---
---
0.6
---
---
0.8
7957
4.82
1.0
7179
4.23
1.2
6368
3.66
NOTES:
High static airflow requires installation of high static kit.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow tables represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.

APPENDIX A BLOWER PERFORMANCE DATA

BELT DRIVE - STANDARD

1
2
CFM
BHP
CFM
---
---
---
---
---
7079
6903
3.32
6405
6198
2.92
5668
5418
2.51
---
---
---
---
1
2
CFM
BHP
CFM
---
---
9359
9018
3.18
8632
8279
2.96
7879
7513
2.73
7097
6716
2.49
---
---
---
---
TURNS OPEN
3
BHP
CFM
BHP
CFM
---
---
0.00
6827
3.20
6623
2.76
6161
2.83
5923
2.41
5434
2.45
5152
2.05
---
---
---
---
---
---
TURNS OPEN
3
BHP
CFM
BHP
CFM
4.92
8991
3.79
8621
4.39
8251
3.39
7867
3.86
7484
2.99
7085
3.35
---
---
---
---
---
---
---
---
24
4
5
BHP
CFM
BHP
2.67
6394
2.28
2.34
5706
1.98
2.02
4949
1.68
---
---
---
---
---
---
---
---
---
---
---
---
4
5
BHP
CFM
BHP
3.54
8188
3.27
3.15
7363
2.85
2.75
---
---
---
---
---
---
---
---
---
---
---
---
---
---
6
CFM
BHP
5982
1.94
5271
1.66
---
---
---
---
---
---
---
---
6
CFM
BHP
7826
3.04
6992
2.63
---
---
---
---
---
---
---
---

Hide quick links: