Gas Btu Input Check (Natural Only); Temperature Rise Check - Daikin GPGM5 Installation Instructions Manual

15.2 seer2 “m” series 2-4 ton single package gas-electric heating & cooling units
Hide thumbs Also See for GPGM5:
Table of Contents

Advertisement

Manifold Pressure Check
1. Turn OFF gas to furnace at the manual gas shutoff
valve external to the furnace.
2. Turn off all electrical power to the system.
3. Back outlet pressure test screw (outlet pressure boss)
out one turn (counterclockwise, not more than one
turn).
4. Attach a hose and manometer to the outlet pressure
boss of the valve.
5. Turn ON the gas supply.
6. Turn on power and energize main (M) solenoid. Do
not energize the HI solenoid.
7. Measure gas manifold pressure with burners firing.
Adjust manifold pressure using the Manifold Gas
Pressure table.
8. Remove regulator cover screw from the low (LO)
outlet pressure regulator adjust tower and turn screw
clockwise to increase pressure, or counterclockwise to
decrease pressure.
9. Energize main (M) solenoid as well as the HI terminal.
10. Remove regulator cover screw from the HI outlet pres-
sure regulator adjust tower and turn screw clockwise
to increase pressure, or counterclockwise to decrease
pressure.
11. Turn off all electrical power and gas supply to the sys-
tem.
12. Remove manometer hose from outlet pressure boss.
13. Turn outlet pressure test screw in to seal pressure
port (clockwise, 7 in-lb minimum).
14. Turn on electrical power and gas supply to the sys-
tem.
15. Turn on system power and energize valve.
16. Using a leak detection solution or soap suds, check
for leaks at pressure boss screw. Bubbles forming in-
dicate a leak. SHUT OFF GAS AND FIX ALL LEAKS
IMMEDIATELY.
.
Mode
White-Rodgers Model 36G54 connected to Manometer
Manifold Gas Pressure
Gas
Low Sta ge
Na tura l
Hi gh Sta ge
Low Sta ge
Propa ne
Hi gh Sta ge
Manifold Gas Pressure
NOTE: For Natural gas to LP gas conversion, Conversion
Kit "LPM-08" must be used. Consult your dealer for appro-
priate conversion kit(s).
Gas BTU Input Check (Natural Gas Only)
To measure the gas input use a gas meter and proceed as
follows:
1. Turn off gas supply to all other appliances except the
unit.
2. With the unit operating, time the smallest dial on the
meter for one complete revolution. If this is a 2 cubic
foot dial, divide the seconds by 2; if it is a 1 cubic foot
dial, use the seconds as is. This gives the seconds
per cubic foot of gas being delivered to the unit.
3. INPUT = GAS HTG VALUE x 3600 / SEC. PER CU-
BIC FOOT
Example: Natural gas with a heating value of 1000 BTU
per cubic foot and 36 seconds per cubic foot as determined
by Step 2, then:
Input = 1000 x 3600 / 36 = 100,000 BTU per Hour.
NOTE: BTU content of the gas should be obtained
from the gas supplier. This measured input must not
be greater than shown on the unit rating plate.
4. Relight all other appliances turned off in step 1. Be
sure all pilot burners are operating.
Main Burner Flame Check
Flames should be stable, soft and blue (dust may cause
orange tips but they must not be yellow) and extending
directly outward from the burner without curling, floating or
lifting off.

Temperature Rise Check

Check the temperature rise through the unit by placing
thermometers in supply and return air registers as close
to the unit as possible. Thermometers must not be able to
sample temperature directly from the unit heat exchangers,
or false readings could be obtained.
1. All registers must be open; all duct dampers must be
in their final (fully or partially open) position and the
unit operated for 15 minutes before taking readings.
2. The temperature rise must be within the range speci-
fied on the rating plate.
NOTE: Air temperature rise is the temperature
difference between supply and return air.
16
Range
Nominal
1.7 - 2.3" w.c.
2.0" w.c.
3.2 - 3.8" w.c.
3.5" w.c.
5.7 - 6.3" w.c.
6.0" w.c.
9.7 - 10.3" w.c.
10.0" w.c.

Advertisement

Table of Contents
loading

Table of Contents