LG ACHH017VBAB Installation And Owner's Manual page 92

Air-cooled inverter scroll heat pump chiller
Table of Contents

Advertisement

ELECTRICAL
Access Holes / Paths
WARNING
• All power wiring and communication cable installation must be performed by authorized service providers working in accordance with local,
state, and National Electrical Code (NEC) regulations related to electrical equipment and wiring, and following the instructions in this manu-
al. Failure to do so will lead to electric shock and bodily injury or death.
• Undersized wiring will lead to unacceptable voltage at the unit and will cause a fire, which will cause bodily injury or death.
• Install appropriately sized breakers / fuses / overcurrent protection switches and wiring in accordance with local, state, and NEC regulations
related to electrical equipment and wiring, and following the instructions in this manual. Generated overcurrent could include some amount
of direct current. Using an oversized breaker or fuse will result in electric shock, physical injury or death.
Access Holes / Paths
1. Power wiring and communication cable access holes and connec-
tions will be different depending on the chiller model and volume.
2. Single Chillers use the connection terminals located at the right
(when viewing from the front).
3. Install the power wiring and communication cables separately
so that communication is not impacted by electric noise (Use
conduits for the power wiring and communication cable, but
do not pass through the same conduit.)
WARNING
• Properly ground the chillers.
refrigerant, gas, or water piping; to lightning rods; to telephone
ground wiring; or to the building plumbing system. Ground wiring
must always be installed by a qualified technician. Ground wiring
is required to prevent accidental electrical shock during current
leakage, which will cause bodily injury or death.
• Install the power wiring only after the ring terminal is connected.
Improper connections can generate a fire, electric shock, physical injury and / or death.
• Install the power wiring only after the ring terminal is connected. Improper connections can damage electrical components.
• Verify the power imbalance is no greater than 2% between phases at each unit. Power imbalances will damage the compressors and other
components.
92
Do not connect ground wire to
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 34: Chiller Wiring / Cable Access Holes.
Right Side
Triple Chiller of 208-230V Models
Dual Chiller
Single Chiller
Triple
Chiller
Left Side