LG ACHH017VBAB Installation And Owner's Manual page 23

Air-cooled inverter scroll heat pump chiller
Table of Contents

Advertisement

REFRIGERANT PIPING AND SENSOR DIAGRAM /
ACHH Hot Water Operation Limits and Performance
145
135
125
115
105
95
85
75
65
55
-20
-10
HOT Water Inlet
Temperature F
HOT Water Outlet
Temperature F
Ambient Range
Approved Δ between EWT and LWT is 4°F to 20°F
Heating Capacity Performance 10°ΔT (EWT to LWT)
100%
90%
80%
70%
60%
50%
40%
30%
20%
-20
-10
OPERATION RANGE AND LIMIT
0
10
20
30
Ambient Air Degrees F
66°F to 127°F
86°F to 131°F
-22°F to 95°F
0
10
20
30
Ambient Air Degrees F
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
40
50
60
1. Proper Glycol Solution is required for Ambient
Operation at or below 41°F
2. LG LATS ISC Selection Software is to be used to
confirm selection and performance.
86°F LWT (-22F/30%, 17F/100%)
105° F LWT (-4F/65%, 32F/100%)
120° F LWT (14F/70%, 32F/100%)
131° F LWT (17F/70%, 41F/100%)
40
50
60
70
80
90
100
70
80
90
100