• Remote desired temperature contact point table
1. Chilled Water Set Point (2 ~ 10 V, 4 ~ 20 mA)
: UI3 (M ode Cool)
500Ω
Volt [V]
[mA]
0.0
0.0
0.2
0.4
0.4
0.8
0.6
1.2
0.8
1.6
No Control (Disconnect-
1.0
2.0
1.2
2.4
1.4
2.8
1.6
3.2
1.8
3.6
3.0
6.0
3.2
6.4
3.4
6.8
3.6
7.2
3.8
7.6
4.0
8.0
4.2
8.4
4.4
8.8
4.6
9.2
4.8
9.6
5.0
10.0
5.2
10.4
5.4
10.8
5.6
11.2
5.8
11.6
6.0
12.0
6.2
12.4
6.4
12.8
6.6
13.2
6.8
13.6
7.0
14.0
7.2
14.4
7.4
14.8
7.6
15.2
7.8
15.6
8.0
16.0
8.2
16.4
8.4
16.8
8.6
17.2
8.8
17.6
9.0
18.0
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Cool Set Point
Cool Set Point
(-10 ~ 20) [°C]
(14 ~ 68) [°F]
No Control (Disconnect-
ed)
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Etc
ed)
14
(Low Temp. Type)
15.8
(Low Temp. Type)
17.6
(Low Temp. Type)
19.4
(Low Temp. Type)
21.2
(Low Temp. Type)
23
(Low Temp. Type)
24.8
(Low Temp. Type)
26.6
(Low Temp. Type)
28.4
(Low Temp. Type)
30.2
(Low Temp. Type)
32
(Low Temp. Type)
33.8
(Low Temp. Type)
35.6
(Low Temp. Type)
37.4
(Low Temp. Type)
39.2
41
42.8
44.6
46.4
48.2
50
51.8
53.6
55.4
57.2
59
60.8
62.6
64.4
66.2
68