Economizer Controller; Controller User Interface And Keypad - Trane BAYECON355 Series Installation Manual

0 to 100% low leak economizer – downflow
Table of Contents

Advertisement

Economizer Controller

N N O O T T I I C C E E
E E l l e e c c t t r r o o s s t t a a t t i i c c D D i i s s c c h h a a r r g g e e ! !
E E l l e e c c t t r r o o s s t t a a t t i i c c d d i i s s c c h h a a r r g g e e c c a a n n s s h h o o r r t t e e q q u u i i p p m m e e n n t t
c c i i r r c c u u i i t t r r y y . .
E E n n s s u u r r e e t t h h a a t t y y o o u u a a r r e e p p r r o o p p e e r r l l y y g g r r o o u u n n d d e e d d b b e e f f o o r r e e
h h a a n n d d l l i i n n g g s s e e n n s s i i t t i i v v e e e e l l e e c c t t r r o o n n i i c c e e q q u u i i p p m m e e n n t t . .
N N o o t t e e s s : :
Upon power up or after a power outage or
brownout (or if power goes below 18 VAC),
the controller begins a 5 5 m m i i n n u u t t e e power up
delay before enabling mechanical cooling.
Power must be above 18 VAC for the delay
to become functional.
The controller will be in "Setup" mode for
the first 6 6 0 0 m m i i n n u u t t e e s s after powered. If a
sensor for outside air or one of the Sylk Bus
devices (sensor or actuator) is disconnected
during the set up mode, the controller will
not alarm that failure. The mixed air
temperature sensor is a system "critical
sensor"; if it is removed during the set up
mode the controller will alarm. After 60
minutes the controller will change to
"Operation" mode and all components
removed or failed will alarm in the operation
mode.
The terminals on MAT, OAT and S-BUS
sensors are polarity insensitive.
Controller User Interface and
Keypad
The user interface consists of an LCD display and a 4-
button keypad on the front of the economizer module.
The LCD is a 16 character by 2 line dot matrix display.
8
Figure 9. Controller user interface and keypad
Table 2. Economizer module - left hand terminal
blocks
Label
Type
Top Left Terminal Block
MAT
20k NTC
MAT
and COM
OAT
20k NTC
OAT
and COM
S-BUS
SYLK Bus
S-BUS
Bottom Left Terminal Block
IAQ 2-10
2-10 Vdc
IAQ COM
COM
IAQ 24V
24 Vac
ACT 2-10
2-10 Vdc
ACT COM
COM
ACT 24V
24 Vac
n/a
Description
Mixed Air Temperature Sensor (polarity
insensitive connection)
Outdoor Air Temperature Sensor
(polarity insensitive connection)
Sylk Bus Sensor (polarity insensitive
connection)
Air Quality Sensor Input (e.g. CO
sensor)
Air Quality Sensor Common
Air Quality Sensor 24 Vac Source
Damper Actuator Output (2-10 Vdc)
Damper Actuator Output Common
Damper Actuator 24 Vac Source
The last pin is not used
RT-SVN044A-EN
2