Trane BAYECON355 Series Installation Manual page 14

0 to 100% low leak economizer – downflow
Table of Contents

Advertisement

E E c c o o n n o o m m i i z z e e r r C C o o n n t t r r o o l l l l e e r r
Table 4. Controller menu structure (continued)
Menu
Parameter
DCVCAL ENA
MAT T CAL
OA T CAL
ADVANCED
OA H CAL
SETUP
RA T CAL
RA H CAL
DA T CAL
2SP FAN DELAY
DAMPER VMIN-HS
DAMPER VMAX-HS
(LS)
DAMPER OPEN
DAMPER CLOSE
CHECKOUT
CONNECT Y1-O
CONNECT Y2-O
CONNECT AUX1-O
CONNECT EXH1
ALARMS(_)
MAT SENS ERR
(e)
CO
SENS ERR
2
14
Parameter
Default Value
MAN
(c)
0.0 F°
(c)
0.0 F°
(c)
0% RH
(c)
0.0 F°
(c)
0% RH
(c)
0.0 F°
(c)
5 Minutes
N/A
N/A
(c)
(c)
N/A
(c)
N/A
(c)
N/A
(c)
N/A
N/A
(c)
(c)
N/A
N/A
(c)
N/A
Parameter
Parameter
Range and
Recommended
Increment
Value
(a)
(b)
MAN (manual)
MAN
AUTO
(+/-2.5°F)
0.0 F°
(+/-2.5°F)
0.0 F°
(+/-10% RH)
0% RH
(+/-2.5°F)
0.0 F°
(+/-10% RH)
0% RH
(+/-2.5°F)
0.0 F°
0 to 20 minutes in
1 minute
5 Minutes
increments.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Notes
Turns on the DCV automatic control of
the dampers. Resets ventilation based
on the RA, OA and MA sensor
conditions. Requires all sensors (RA,
OA, MA and CO
). This operation is not
2
operable with a 2-speed fan unit.
Allows for the operator to adjust for an
out of calibration temperature sensor.
Allows for the operator to adjust for an
out of calibration temperature sensor.
Allows for the operator to adjust for an
out of calibration humidity sensor.
Allows for the operator to adjust for an
out of calibration temperature sensor.
Allows for the operator to adjust for an
out of calibration humidity sensor.
DA T CAL is not available.
When in economizing mode this is the
delay for the high speed fan to try to
satisfy the call for second stage cooling
before the first stage mechanical
cooling is enabled.
Positions damper to VMIN position.
Positions damper to VMAX position.
With 2-speed fan units the damper will
position to VMAX low speed fan.
Positions damper to the full open
position. Exhaust fan contacts enable
during the DAMPER OPEN test. Make
sure you pause in this mode to allow
for exhaust contacts to energize due to
the delay in the system.
Positions damper to the fully closed
position.
Closes the Y1-O relay (Y1-O). See
Step
N/A
CONNECT AUX1 O energizes the
AUX1-O output. If AUX1-O setting is:
NONE — No action taken
ERV — 24 Vac out. Turns on or
signals an ERV that the conditions
are not good for economizing but
are good for ERV operation.
SYS — 24 Vax out. Issues a
system alarm.
Closes the power exhaust fan 1 relay
(EXH1).
RT-SVN044A-EN