Operator's
Manual
TABLE OF CONTENTS
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . .
Mounting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Connections
Engine Starting & Auxiliary Circuits
Functional Test
. . . . . . . . . . . . . . . .
TESTING & SERVICE
Transfer Test
. . . . . . . . . . . . . . . . . . . . . . . . . .
Preventive Maintenance
Disconnecting the Controller
Manual Load Transfer
Trouble-Shooting
. . . . . . . . . . . . . . . . . . . . . .
BYPASSING & ISOLATING
Bypassing the ATS
Isolating the ATS
. . . . . . . . . . . . . . . . . . . . . .
Return to Service
. . . . . . . . . . . . . . . . . . . . . .
INDEX
. . . . . . . . . . . . . . . . . . . . . . . . .
An experienced licensed electrician must install ATB
Typical 7000 Series ATB catalog no. for overlapping neutral, 3 pole, 4000 amp, 480 V, in Type 1 enclosure:
7ATB
Neutral
A
– solid
C
– overlapping
blank --- none
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO)
Bypass–Isolation Switches
F–design, 3000 and 4000 amp. sizes
section-page
1-1
1-1
. . . . . . . . . . . . . . . . . . . .
1-2
. . . . . .
1-2
1-5, 1-6, 1–7
. . . . . . . . . . . . . . . . . .
2-1
2-1
. . . . . . . . . . . . . . . .
2-1
. . . . . . . . . . . .
2-1
. . . . . . . . . . . . . . . . . .
2-2
2-2
. . . . . . . . . . . . . .
3-1
. . . . . . . . . . . . . . . . . . . .
3-1
3-1
3-3
back cover
Catalog Number Identification
C
3
Phase Poles
Amperes
2
– single Ø
3
– three Ø
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com
7000 Series ATB
Automatic Transfer &
Refer to the outline and wiring drawings provided
with your 7000 Series ATB for all installation and
connection details and accessories.
Refer to Group 5 Controller User's Guide 381333–126
for ATS status display messages, time delays, pickup
& dropout settings, and adjustments.
Each 7000 Series ATB contains a rating label to define the
loads and fault circuit withstand/closing ratings. Refer to the
label on the Transfer Switch for specific values.
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
The Transfer Switch nameplate includes data for each
specific 7000 Series ATB. Use the switch only within the
limits shown on this nameplate. A typical Catalog Number
is shown below with its elements explained:
4000
N
Voltage
A
J
3000
115
4000
B
K
120
C
L
208
D
M
220
E
N
230
F
P
240
G
Q
277
H
R
380
Rating Label
!
Nameplate
5
C
Controller
5
– standard
400
5X
– if accesso-
415
ries ordered
440
460
480
550
575
600
381333–133 A
www.asco.ca
Enclosure
C
– type 1
F
– type 3R
G
– type 4
L
– type 12
blank – open type