The number of indoor units that can be connected to an outdoor unit is as defined in the following table:
Outdoor Unit Type
RAS-3.0HNSKQ
RAS-3.5HNSKQ
RAS-4.0HNSKQ
RAS-4.5HNSKQ
RAS-5.0HNSKQ
RAS-6.0HNSKQ
RAS-6.5HNSKQ
RAS-7.0HNSKQ
NOTE:
◆ The connectable indoor unit capacity ratio can be calculated as follows:
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity.
◆ For the same system, if the connectable indoor unit capacity ratio is over than 100%, and which all the
indoor units operate simultaneously, the capacity of every indoor unit should be less than its rated capacity.
◆ Indoor unit and outdoor unit connected to the total capacity of indoor units for the outdoor unit rated capacity of
50% to 130%.
Table 2.2 System Combination
Min. Total Capacity
Rated
of the indoor units
Capacity
can be connected
(kW)
(kW)
8.0
4
10.0
5
11.2
5.6
12.5
6.25
14.0
7
16.0
8
18.0
9
20.0
10
Max. Total Capacity
of the indoor units
can be connected
(kW)
10.4
13
14.56
15.6
18.2
20.8
23.4
26
10
Numbers of the
Min. Capacity
indoor units can
at Individual
be
Operation (kW)
connected(Q'ty)
2~4
2~5
2~5
2~5
2~6
2~6
2~9
2~10
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8