HIDRIA 0314-4-0089 Operating Instructions Manual

Fan with electronically commutated external-rotor motor

Advertisement

Quick Links

INSTALLATION, MAINTENANCE AND USER'S GUIDE
FAN WITH ELECTRONICALLY COMMUTATED EXTERNAL-ROTOR MOTOR
&
Note :
Be sure to familiarize yourself with these instructions before working on this unit. Not paying attention to these warnings
and instructions may lead to malfunctions and failures or may seriously endanger human life.

Table of Contents :

01
02
TYPICAL FEATURES AND PROPER USE
03
04
05
06
07
08
09
10
11
12
Fan Code:
0314-4-0089
Fan type : R14R-56APS-ET60B-03B18
Symbols :
WARNING - to indicate warning situation
NOTE - indicate valuable information

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 0314-4-0089 and is the answer not in the manual?

Questions and answers

Summary of Contents for HIDRIA 0314-4-0089

  • Page 1: Table Of Contents

    INSTALLATION, MAINTENANCE AND USER'S GUIDE FAN WITH ELECTRONICALLY COMMUTATED EXTERNAL-ROTOR MOTOR Fan Code: 0314-4-0089 Fan type : R14R-56APS-ET60B-03B18 & Note : Be sure to familiarize yourself with these instructions before working on this unit. Not paying attention to these warnings and instructions may lead to malfunctions and failures or may seriously endanger human life.
  • Page 2: Safety

    The risk of pulling into rotating part. Do not wear any loose clothing (e.g. tie) or jewellery. Long hair must be protected with a cap. Risk of injury! 2 / 9 © Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.
  • Page 3 Maintenance free ball-bearings and dynamically balanced rotating parts. Control circuit is SELV isolated from main power supply (including an external power supply for sensors). 3 / 9 © Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.
  • Page 4: Operating Conditions

    - IEC 60034-1 - Data on the nameplate established at a point of nominal load according to standard for Rotational electrical machines. Airflow volume max., qV: 10141 m³/h Pressure Increase max., ps: 359 Pa 4 / 9 © Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.
  • Page 5: Installation And Connection

    PE symbol. More information about dimensions of second PE conductor please find in guidelines of mentioned EN or equivalent standard (a cross-section of second Cu conductor should never be less than 2.5mm 5 / 9 © Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.
  • Page 6 Sensor supply : +10V - GND or +20V - GND Slave control : OUT-GND The device is compatible with Modbus protocol RTU. Please read additional instructions about Hidria EC Modbus parameters and additional information for general purpose using MODBUS (www.modbus.org) .
  • Page 7: Speed Control

    Rotation speed of a variable speed fan can be controlled by various signals: - Linear voltage input (0-10V) or current input (4-20mA) or PWM input (PWM duty cycle 0-100%). - MODBUS RTU protocol (Additional information are in documentation "Hidria EC Modbus parameters" and on www.modbus.org. - Slave control output.
  • Page 8: Putting Into Operation

    In the specific case, the undervoltage protection may switch off the fan to stand-by mode, for example, fan running or testing at high pressure drop and low voltage. Over temperature protection: Internally connected thermal overload protector to protect electronic and motor against over temperature. 8 / 9 © Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.
  • Page 9: Maintenance, Service And Cleaning

    The manufacturer will not accept liability for any resulting damages caused by the non-observance of this manual or any unauthorized modification to the system. 9 / 9 © Copyright HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.