Assurance Emergency Lighting Cold Pack L10-ET-CEC Sereis Installation Instructions Manual

Emergency led driver

Advertisement

Emergency LED Driver
Installation Instructions
Cold Pack L10-ET-CEC & L10-ETSB-CEC Series
Class 2 Output (Only for nominal voltage series 15-55V)
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Do not join battery connector until installation is complete and AC power is supplied to the emergency driver.
2. This product is intended for use with an emergency LED lighting load and supplies nominal power and a
maximum voltage in emergency mode for a minimum of 90 minutes.
3. An unswitched AC power source is required (115-277 VAC, 50/60 Hz) to power these units.
4. This product's chassis must be grounded.
5. This product is suitable for use in damp locations where the ambient temperature is -20℃minimum, to 55℃
maximum. This product is also suitable for installation in sealed and gasketed fixture. This product is not suitable
for heated air outlets and wet or hazardous locations.
6. This product contains a rechargeable Lithium-ion battery. The battery must be recycled or disposed of properly.
7. Make certain all connectors are in accordance with the National Electrical Codes and any local regulations.
8. This emergency LED driver is suitable for both factory or field installation. For field installation, please see the
instructions section.
9. Do not install near gas or electric heaters.
10. The use of accessory equipment is not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for applications other than the intended use.
12. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by
unauthorized personnel.
13. This device complies with part 15 of the FCC Rules. Operation is suitable to the following two conditions: (1) This
device may not cause harmful interference, and (2) This device must accept any interference that may cause
undesired operation.
14. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and disconnect the
battery connector of the emergency driver before servicing.
15. Do not attempt to service the battery. It is a sealed, no-maintenance battery is used that is not field replaceable.
Contact the manufacturer for information on service.
16. Servicing should be performed by qualified service personnel only.
357 Cumberland Street Memphis, TN 38112
1
Tel: 1-877-774-4775

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Cold Pack L10-ET-CEC Sereis and is the answer not in the manual?

Questions and answers

Summary of Contents for Assurance Emergency Lighting Cold Pack L10-ET-CEC Sereis

  • Page 1 Emergency LED Driver 357 Cumberland Street Memphis, TN 38112 Tel: 1-877-774-4775 Installation Instructions Cold Pack L10-ET-CEC & L10-ETSB-CEC Series Class 2 Output (Only for nominal voltage series 15-55V) READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. Do not join battery connector until installation is complete and AC power is supplied to the emergency driver. 2.
  • Page 2 INSTALLATION CAUTION: DO NOT JOIN BATTERY CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY DRIVER. NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency driver must be fed from the same branch circuit as the AC driver.
  • Page 3 NOTE: Considerations must be made to protect the wires on the models have no flexible conduit if installed outside of the luminaire. Note: If the application requires the emergency LED driver to be mounted on top of the luminaire, please use the models which provide metal flexible conduit instead of bare wire.
  • Page 4 STEP #3 WIRING THE EMERGENCY DRIVER Select the appropriate wiring diagram to connect the emergency driver to the AC driver and LED load. Make sure all connections are in accordance with the National Electrical Code and any local regulations. After installation is complete, supply AC power to the emergency driver and turn on battery switch/join battery connector.
  • Page 5 TCASE TEST POINT LOCATION L10-ETSB-CEC L10-ET-CEC EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICALLY. IT MAY BE USED WITH OTHER DRIVERS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. SYSTEM WIRING DIAGRAM Figure A. L10-ET-CEC with Internal Battery Option 1. Figure B.
  • Page 6 Figure C. L10-ETSB-CEC with External Battery Option 1. Figure D. L10-ETSB-CEC with External Battery Option 2. Figure E. L10-ET-CEC Only (Without AC Driver)
  • Page 7 Figure F. L10-ETSB-CEC Only (Without AC Driver) Figure G. Multiple Luminaires with Dimming Drivers NOTE: A short-term discharge test may be conducted after the emergency driver has been charged for one hour. A 24-hour charging period must be performed before conducting a long-term discharge test. Refer to the OPERATION section.

This manual is also suitable for:

Cold pack l10-etsb-cec series

Table of Contents