Important information regulation
regarding the refrigerant used
This product contains fluorinated greenhouse gases. Do
not vent gases into the atmosphere.
CaUtIon
• Inform user if system contains 5 tCO
of fluorinated greenhouse gases. In this case, it
has to be checked for leakage at least once every
12 months, according to regulation n°517/2014.
This activity has to be covered by qualified
personnel only. In case situation above (5 tCO
or more of R-410A), installer (or recognized
person which has responsibility for final check)
has to provide a maintenance book, with all the
information recorded according to REGULATION (EU)
No 517/2014 OF THE EUROPEAN PARLIAMENT AND
OF THE COUNCIL of 16 April 2014 on fluorinated
greenhouse gases.
DB68-05916A-09_IM_DVM Chiller Outdoor_EU_EN_.indd 81
Please fill in the following indelible ink on the
refrigerant charge label supplied with this product on
and on this manual.
f ♳ : The factory refrigerant charge of the product.
f ♴ : The additional refrigerant amount charged in the
field.
f ♳+♴ : The total refrigerant charge.
e or more
2
e
2
Unit
♳, a
♴, b
♳+♴, c
Refrigerant type
• GWP = Global Warming Potential
• Calculating tCO
notE
• ⓐ: Factory refrigerant charge of the product: see
unit name plate.
• ⓑ: Additional refrigerant amount charged in the
field. (Refer to the above information for the
quantity of refrigerant replenishment.)
• ⓒ: Total refrigerant charge.
• ⓓ: Refrigerant cylinder and manifold for charging.
CaUtIon
• The filled-out label must be adhered in the
proximity of the product charging port. (ex. onto
the inside of the stop valve cover.)
Indoor unit
Outdoor unit
02
ⓓ
kg
GWP value
R-410A
e : kg x GWP / 1000
2
01
tCo
e
2
2088
81
English