Samsung AG042KSV Series Installation Manual page 38

Dvm chiller
Table of Contents

Advertisement

Electrical wiring work
no.
name
Set
temperature/
17-18
room
temperature
C-t/B
sensor
External
19-20
water outlet
temperature
• Usual input: Operate by current status of contact
Instant input: Operate when contact signal changes from OFF to ON / from ON to OFF
Note1)
Value of water outlet set temperature = 5.625 x Current - 32.5
Heat (Hot water) mode recognizes minimum 25 °C and maximum 55 °C
Cool (Cool storage) mode recognizes minimum 5 °C and maximum 25 °C (Minimum -10 °C when using low
temperature function)
Current (ma)
temperature (°C)
Note2)
Room temperature = 6.25 x Current - 75
Current (ma)
temperature (°C)
If operation pattern is not standard control, control standard temperautre depends on external water outlet
Note3)
temperature sensor. External water outlet temperautre sensor should be installed where can represent the
temperature of water pipe system.
Water outlet temperature = 6.25 x current -55
Current (ma)
temperature (°C)
Operates when input method for quiet function is set as external contact
Note4)
- If the contact is short, quiet function operates in Cool/Heat mode.
- Quiet function by Module Control operates in Cool mode and night time.
Note5)
Operates when input method for demand function is set as external contact
Note6)
Operates when input method for forced fan function is set as external contact
Note7)
Operates when input method for water law function is set as external contact
Main unit of module when group is not available
Note8)
38
English
DB68-05916A-09_IM_DVM Chiller Outdoor_EU_EN_.indd 38
Signal
Function
Recognize water outlet set temperature
by external input (4 ~ 20 mA)
Analog
Recognize value of room temperature
current
sensor (4 ~ 20 mA) when standard for
water law is room temperautre
Recognize external water outlet
Analog
temperature by external temperature
current
sensor (4 ~ 20 mA)
Note3)
4
6
8
-10.00
1.25
12.50
4
6
8
-50.00
-37.50
-25.00
4
6
8
-30.00
-17.50
-5.00
Contact on
Contact off
(Short)
(open)
Note1)
-
-
Note2)
-
-
10
12
14
23.75
35.00
46.25
10
12
14
-12.50
0.00
12.50
10
12
14
7.50
20.00
32.50
Maximum
Signal
Setting unit
allowable
recognition
current
Current
Main unit of
20 mA
input
group
Note8)
Current
Main unit of
20 mA
input
group
Note8)
16
18
20
57.50
68.75
80.00
16
18
20
25.00
37.50
50.00
16
18
20
45.00
57.50
70.00
2022-05-02 오전 9:00:04