15.
UPDATE
– Set the display & analogue output update time [Default 1000MS]
Press increment
must be selected in order for the rate controller to function.
100 MS
= 100ms (0.1s)
250 MS
= 250ms (0.25s)
500 MS
= 500ms (0.5s)
1000 MS
= 1000ms (1s)
3000 MS
= 3000ms (3s)
Press settings
16.
LOCKED
– Lock settings [Default NO]
Once locked is set to yes, upon entering run mode the values of all settings are
maintained but cannot be altered without first performing an unlock.
Press increment
NO
= Not locked, all settings are accessible in the set menu.
YES
= Locked, the set menu and sensitivity adjustment can no longer be accessed
without unlocking via the reset terminal.
Press settings
Setting the Sensitivity
The sensitivity can only be altered in Frequency A mode or Frequency B mode, and this will
set the sensitivity value for the respective input only. Press and hold the settings button ,
then press the select
the current value is displayed. Sensitivity ranges from 0 (least sensitive) to 63 (most sensitive).
If the lock has been activated in the settings menu, the display will instead show "LOCKED",
and the unit must first be unlocked following the "Unlock the Settings" procedure below to
adjust the sensitivity
Press select
←
to reduce the value or increment
being touched the unit will apply the selected sensitivity value and return to run mode. It is
recommended that the sensitivity level is set only as high as necessary to obtain a steady
signal. This minimises the risk of detecting spurious signals.
↑
to select from the below options. One of these output modes
or select
←
to move to the next setting.
↑
to change between from the below options.
or select
←
to return to the mode setting.
[Default 50]
←
button to enter sensitivity mode The display will show
↑
to increase it. After 2s of neither button
15
SENS
and then