Download Print this page

ETC Paradigm P-TS7-E Installation Manual page 3

Wall-mount touchscreen

Advertisement

ETC Installation Guide
P-TS7-E Touchscreen
Connect Ethernet
Note:
standard.
1. Terminate the network wiring in the provided RJ45 punchdown block using a standard
110 punchdown tool (not provided). The connector is labeled for Cat5e wire termination
color code. Do not pre-strip the conductors, the punchdown connector provides insulation
displacement.
2. Snap the connector into the bracket.
Connect Auxiliary Power and ESD Ground
Terminate the incoming wiring to the provided Auxiliary Power and ESD Ground wire pigtails.
1. Connect the ESD ground wire pigtail.
a. Strip 11 mm (7/16 in) of insulation from the ends of
the station ground wire pigtail, provided in the
termination kit, and the incoming ground wire.
b. Use one WAGO
termination kit, to connect the station ESD ground
pigtail and the incoming ground. For stations using
grounded metal conduit, connect the ground pigtail
to the metal back box ground location.
c. Install the ESD ground wire pigtail to the spade terminal on the termination board.
2. Terminate and connect 24 VDC Auxiliary Power. Use copper conductors only, typically a
1.5 mm
a. Strip 11 mm (7/16 in) from the ends of each conductor (Aux Power pigtail provided and
the installed power wires).
b. Use the provided WAGO connectors to connect the power pigtail and the installed power
wires. One WAGO should be used for the red pair (power +) and one for the black wire
pair (power -). Open the terminal levers on the WAGO connector and insert the installed
wire and the lead from the pigtail to into the terminals, and then close the levers.
c. Install the two-position connector from the pigtail to the mating receptacle on the
termination board.
P-TS7-E Touchscreen
All Ethernet terminations must follow IEEE 802.3 and be terminated to the T568B
®
connector, provided in the
2
(16 AWG) black and red wire pair.
Page 3 of 4
ETC

Advertisement

loading